Yokogawa EJA118 User Manual

Page 34

Advertising
background image

IM 1C22H1-01E

7-5

7. BRAIN TERMINAL BT200 OPERATION

T0706.EPS

Auxiliary setting data 1

D

Menu name

AUX SET 1

NORMAL/REVERSE
NORMAL/REVERSE**

Output reversal

D40 REV OUTPUT

Impulse piping
accessing direction

D45 H/L SWAP

HIGH/LOW

CPU error

D52 BURN OUT

–19999 to 19999

Engineering range,
lower range value

D22 DISP LRV

–19999 to 19999

Engineering range,
higher range value

D23 DISP HRV

deg C/deg F

Temperature setting
units

D30 TEMP UNIT

Selected from mmH

2

O, mmAq,

mmWG, mmHg, Torr, Pa, hPa, kPa,
MPa, mbar, bar, gf/cm

2

, kgf/cm

2

,

inH

2

O, inHg, ftH

2

O, psi, or atm

Static pressure setting
units

D31 STAT. P. UNIT

Hardware error

D53

Same as A60

HOLD/HIGH/LOW

ERROR OUT

Self-diagnostic
messages

D60 SELF CHECK

Auxiliary setting data 2

E

OFF/ON

Menu name

AUX SET 2

Bidirectional mode

E30 BI DIRE

MODE

Same as A60

Self-diagnostic
messages

E60 SELF CHECK

No.

Description

Remarks

Item

Menu name

Automatic setup

H

AUTO SET

Adjustment data

J

–5 to 110.0%

Menu name

ADJUST

Automatic zero
adjustment

J10 ZERO ADJ

Manual zero
adjustment

J11 ZERO DEV.

ENABLE/INHIBIT

External zero-
adjustment screw
permission

J20 EXT. ZERO

ADJ

Same as A60

Self-diagnostic
messages

J60 SELF CHECK

Display the error

History of the errors

RECORD

Last error

P10

P11

ERROR REC 1

Display the error

One time before

ERROR REC 2

P12

Display the error

Two time before

ERROR REC 3

Menu name

Tests

K

TEST

–5 to 110.0% Displays ‘ACTIVE’
while executing

Test output % setting

K10 OUTPUT in %

Same as A60

Self-diagnostic
messages

K60 SELF CHECK

Menu name

Memo

M

P

MEMO

8 uppercase alphanumerics

Memo

M10 MEMO 1

8 uppercase alphanumerics

Memo

M20 MEMO 2

8 uppercase alphanumerics

P13

Display the error

Three time before

ERROR REC 4

P60

Same as A60

Self-diagnostic
messages

SELF CHECK

Memo

M30 MEMO 3

8 uppercase alphanumerics

Memo

M40 MEMO 4

8 uppercase alphanumerics

Memo

M50 MEMO 5

Same as A60

Self-diagnostic
messages

M60 SELF CHECK

–32000 to 32000

Automatic measure-
ment range lower
range value setup

H10 AUTO LRV

–32000 to 32000

Automatic
measurement range
higher range value
setup

H11 AUTO HRV

Same as A60

Self-diagnostic
messages

H60 SELF CHECK

Applica-

bility

P L

F

8 uppercase
alphanumerics

Engineering unit for
display

D21 DISP UNIT

As specified when ordered.

As specified when ordered.

deg C

As specified when ordered.
If not specified, MPa.

If not specified, NORMAL.
NORMAL

HIGH

HIGH

OFF

Displays the same data as
C21.

Displays the same data as
C22.

Rewrita-

bility

Default Value

** Not applicable for Model EJA115.