5 grounding, 6 power supply voltage and load resistance – Yokogawa EJA118 User Manual

Page 25

Advertising
background image

IM 1C22H1-01E

5-4

5. WIRING

᭿ Flameproof metal conduit wiring
• A seal fitting must be installed near the terminal box

connection port for a sealed construction.

• Apply a non-hardening sealant to the threads of the

terminal box connection port, flexible metal conduit
and seal fitting for waterproofing.

F0510.EPS

Non-hazardous area

Hazardous area

Flameproof
heavy-gauge
steel conduit

Tee

Drain plug

Seal fitting

Gas sealing device

Flameproof flexible
metal conduit

Apply a non-hardening
sealant to the threads of
these fittings for
waterproofing

After wiring, impregnate the fitting
with a compound to seal tubing.

Figure 5.4.2d Typical Wiring Using Flameproof Metal

Conduit

5.5 Grounding

(a) Grounding should satisfy JIS Class 3 requirements

(grounding resistance, 100

or less). Grounding is

required for JIS flameproof type and intrinsically
safe type.

(Note) If equipped with built-in Lightning Protector, grounding

should satisfy Special JIS class 3 requirements (grounding
resistance, 10

or less).

(b) There are ground terminals on the inside and

outside of the terminal box. Either of these termi-
nals may be used.

(c) Use 600 V grade PVC insulated wires for ground-

ing.

Ground terminal

Ground terminal

Transmitter terminal box

F0511.EPS

Figure 5.5 Ground Terminals

5.6 Power Supply Voltage and

Load Resistance

When configuring the loop, make sure that the external
load resistance is within the range in the figure below.

(Note) In case of an intrinsically safe transmitter, external load

resistance includes safety barrier resistance.

,









600

250

0

10.5

16.4

24.7

42

External

load

resistance

R (

)

Power supply voltage E (V DC)

F0512.EPS

Communication

applicable range

BRAIN and HART

R=

E–10.5

0.0236

Figure 5.6 Relationship between Power Supply Voltage

and External Load Resistance

Advertising