3 starting operation, 4 shutting down operation – Yokogawa EJA118 User Manual

Page 28

Advertising
background image

IM 1C22H1-01E

6-3

6. OPERATION

᭿

Using the Transmitter Zero-Adjustment

Screw

Turn the screw to match the output signal to the actual
measured value in %.

᭿

Using the BT200

Select the parameter

J10: ZERO ADJ.

Change the

set point (%) displayed for the parameter to the actual
measured value (%), and press the

ENTER

key twice.

See Subsection 7.3.3 (12) for operation details.

Change setting to the actually

measured value (40.0%).

Press

key twice

for 40% output 10.4 mA DC.

SET
J10:ZERO ADJ
–0.0 %
+ 040.0

CLR

ESC

F0606.EPS

A display at J10

SET
J10:ZERO ADJ
–0.0 %
+ 000.0

CLR

ESC

6.3 Starting Operation

After completing the zero point adjustment, use the
procedure below to start operation.

1) Confirm the operating status.

There will be cases in which the output signal
exhibits wide fluctuations (hunting) due to periodic
variation in the process pressure. In such cases,
BT200 operation can dampen the transmitter
output signal. Confirm the hunting using a receiv-
ing instrument or the integral indicator, and set the
optimum damping time constant. See Subsection
7.3.3 (3), “Damping Time Constant Setup.”

2) After confirming the operating status, perform the

following.

IMPORTANT

• Remove the BT200 from the terminal box, and

confirm that none of the terminal screws are
loosened.

• Close the terminal box cover and the amplifier

cover. Screw each cover in tightly until it will
not turn further.

• Two covers are required to be locked on the

CENELEC, SAA, and JIS Flameproof type
transmitters. An Allen head bolts (shrouding
bolts) are provided under edge of the each
cover for locking. When a shrouding bolts are
driven counterclockwise by an Allen wrench, it
is coming out and locks up a cover. (See page
8-4)
After locking, the covers shoud be confirmed
not to be opened.

• Tighten the zero-adjustment cover mounting

screw to fix the cover in position.

6.4 Shutting Down Operation

Turn off the power.

NOTE

Whenever shutting down the transmitter for a
long period, detach the transmitter (diaphragm
seals) from the tank.

Advertising