IM 1C22H1-01E

5-3

5. WIRING

5.4.2 Wiring Installation

(1) General-use Type and Intrinsically Safe

Type

Make cable wiring using metallic conduit or water-
proof glands.

• Apply a non-hardening sealant to the terminal box

connection port and to the threads on the flexible
metal conduit for waterproofing.

F0507.EPS

Flexible metal conduit

Wiring metal
conduit

Tee

Drain plug

Apply a non-hardening
sealant to the threads for
waterproofing.

Figure 5.4.2a Typical Wiring Using Flexible Metal Conduit

(2) Flameproof Type (JIS)

Wire cables through a flameproof packing adapter, or
using a flameproof metal conduit.

᭿ Wiring cable through flameproof packing adapter
for only JIS flameproof type (see Figure 5.4.2b).
• Use only flameproof packing adapters approved by

Yokogawa.

• Apply a nonhardening sealant to the terminal box

connection port and to the threads on the flameproof
packing adapter for waterproofing.

Flameproof packing adapter

Flexible metal conduit

Wiring metal
conduit

Tee

Drain plug

Apply a non-hardening
sealant to the threads for
waterproofing.

F0508.EPS

Figure 5.4.2b Typical Cable Wiring Using Flameproof

Packing Adapter

• Measure the cable outer diameter in two directions to

within 1 mm.

• Calculate the average of the two diameters, and use

packing with an internal diameter nearest to this value
(see Table 5.4.2).

Table 5.4.2

Flameproof Packings and Applicable Cable
Outer Diameters

T0501.EPS

G9601AM

8 to 10

10.1 to 12

16 8-10
16 10-12

G 1/2

G11

G12

Optional

Code

Wiring Port

Thread

Diameter

Applicable

Cable OD

(mm)

Identifying

Mark

Part

Number

• Mounting flameproof packing adapter body to conduit

connection (see Figure 5.4.2c)

1) Screw the flameproof packing adapter into the

terminal box until the O-ring touches the wiring
port (at least 6 full turns), and firmly tighten the
lock nut.

2) Insert the cable through the union cover, the union

coupling, the clamp nut, the clamp ring, the gland,
the washer, the rubber packing, and the packing
box, in that order.

3) Insert the end of the cable into the terminal box.
4) Tighten the union cover to grip the cable. When

tightening the union cover, tighten approximately
one turn past the point where the cable will no
longer move up and down.
Proper tightening is important. If it is too tight, a
circuit break in the cable may occur; if not tight
enough, the flameproof effectiveness will be
compromised.

5) Fasten the cable by tightening the clamp nut.
6) Tighten the lock nut on the union cover.
7) Connect the cable wires to each terminal.

O-ring

Adapter body

Lock nut

Wrench

Packing box

Rubber packing

Washer

Gland

Clamp ring

Clamp nut

Union coupling

Lock nut

Wrench

Union cover

Cable

Apply a non-hardnening
sealant to the threads for
waterproofing.

F0509.EPS

Figure 5.4.2c Installing Flameproof Packing Adapter

Advertising