2. HANDLING CAUTIONS

• Entity Installation Requirements

Vmax

≥ Voc or Vt, Imax ≥ Isc or It,

Pmax (IS Apparatus)

≥ Pmax (Barrier)

Ca

≥ Ci + Ccable, La ≥ Li + Lcable

Note 3. Installation

• Barrier must be installed in an enclosure that meets

the requirements of ANSI/ISA S82.01.

• Control equipment connected to barrier must not use

or generate more than 250 V rms or V dc.

• Installation should be in accordance with ANSI/ISA

RP12.6 “Installation of Intrinsically Safe Systems for
Hazardous (Classified) Locations” and the National
Electric Code (ANSI/NFPA 70).

• The configuration of associated apparatus must be

FMRC Approved.

• Dust-tight conduit seal must be used when installed

in a Class II, III, Group E, F and G environments.

• Associated apparatus manufacturer’s installation

drawing must be followed when installing this
apparatus.

• The maximum power delivered from the barrier

must not exceed 0.9 W.

• Note a warning label worded “SUBSTITUTION OF

COMPONENTS MAY IMPAIR INTRINSIC
SAFETY,” and “INSTALL IN ACCORDANCE
WITH DOC. No. IFM012-A12 P.1 and 2.”

Note 4. Maintenance and Repair

• The instrument modification or parts replacement by

other than authorized representative of Yokogawa
Electric Corporation is prohibited and will void
Factory Mutual Intrinsically safe and Nonincendive
Approval.

F0203.EPS

Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G

EJA Series Pressure
Transmitters

EJA Series Pressure
Transmitters

Safety Barrier

Supply

Supply

Hazardous Location

Nonhazardous Location

Hazardous Location

Nonhazardous Location

General
Purpose
Equipment

+

+

+

+

+

+

[Intrinsically Safe]

Class I, II, Division 2,
Groups A, B, C, D, E, F, G
Class III, Division 1.

Not Use
Safety Barrier

[Nonincendive]

General
Purpose
Equipment

b. FM Explosionproof Type

Caution for FM explosionproof type.

Note 1. Model EJA Series differential, gauge,

and absolute pressure transmitters with
optional code /FF1 are applicable for
use in hazardous locations.

• Applicable Standard: FM3600, FM3615, FM3810,

ANSI/NEMA250

• Explosionproof for Class I, Division 1, Groups B,

C and D.

• Dust-ignitionproof for Class II/III, Division 1,

Groups E, F and G.

• Outdoor hazardous locations, NEMA 4X.
• Temperature Class: T6
• Ambient Temperature: –40 to 60

°C

• Supply Voltage: 42 V dc max.
• Output signal: 4 to 20 mA

Note 2. Wiring

• All wiring shall comply with National Electrical

Code ANSI/NEPA70 and Local Electrical Codes.

• When installed in Division 1, “FACTORY

SEALED, CONDUIT SEAL NOT REQUIRED.”

Note 3. Operation

• Keep the “CAUTION” nameplate attached to the

transmitter.
CAUTION: OPEN CIRCUIT BEFORE REMOV-
ING COVER. SEAL ALL CONDUITS WITHIN
18 INCHES. WHEN INSTALLED IN DIV.1,
“FACTORY SEALED, CONDUIT SEAL NOT
REQUIRED.” INSTALL IN ACCORDANCE
WITH THE INSTRUCTION MANUAL IM 1C22.

• Take care not to generate mechanical sparking

when accessing to the instrument and peripheral
devices in a hazardous location.

Note 4. Maintenance and Repair

• The instrument modification or parts replacement

by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void Factory Mutual Explosionproof Ap-
proval.

c. FM Intrinsically Safe Type/FM

Explosionproof Type

Model EJA Series pressure transmitters with
optional code /FU1 can be selected the type
of protection (FM Intrinsically Safe or FM
Explosionproof) for use in hazardous loca-
tions.