Brain terminal bt200, 1 bt200 operation precautions, 1 connecting the bt200 – Yokogawa EJA530A User Manual

Page 32: 2 conditions of communication line, 2 bt200 operating procedures, 1 key layout and screen display, Brain terminal bt200 operation -1, Bt200 operation precautions -1, Connecting the bt200 -1, Conditions of communication line -1

Advertising
background image

IM 01C21F01-01E

8-1

8. BRAIN TERMINAL BT200 OPERATION

8.

BRAIN TERMINAL BT200
OPERATION

The DPharp is equipped with BRAIN communica-
tions capabilities, so that range changes, Tag No.
setup, monitoring of self-diagnostic results, and zero
point adjustment can be handled by remote control
via BT200 BRAIN TERMINAL or CENTUM CS
console. This section describes procedures for setting
parameters using the BT200. For details concerning
the BT200, see IM 01C00A11-01E, “BT200 User’s
Manual.”

8.1 BT200 Operation Precau-

tions

8.1.1 Connecting the BT200

The transmitter and the BT200 can be connected
either to the BT200 connection hooks in the transmit-
ter terminal box or to a relaying terminal board.

Relaying

terminals

Distributor

Control room

Terminal board

F0801.EPS

Figure 8.1.1 Connecting the BT200

8.1.2 Conditions of Communication Line

DPharp

BT200

Cable

resistance Rc

Cable resistance Rc

Load

resistance R

cc

Power
supply

᭹ Loop resistance = R + 2Rc

= 250 to 600 Ω

᭹ Loop capacitance = 0.22 µF max.

F0802.EPS

Figure 8.1.2 Conditions of Communication Line

8.2 BT200 Operating Procedures

8.2.1 Key Layout and Screen Display

Figure 8.2.1a shows the arrangement of the operating
keys on the BT200 keypad, and Figure 8.2.1b shows
the BT200 screen component.

F0803.EPS

LCD
(21 character × 8 lines)

Movement keys

Power ON/OFF key

Function keys

ENTER key

Alphanumeric keys

Shift keys

Figure 8.2.1a BT200 Key Layout

PARAM
A10:OUTPUT
100.0 %
A11:ENGR. OUTPUT
1000 mmH20
A20:AMP TEMP
23 deg C

Menu choices

Messages

MENU SCREEN

Screen title

MENU
A:DISPLAY
B:SENSOR TYPE

BATTERY

HOME

SET

ADJ

ESC

Function

commands

PARAMETER SCREEN

Parameters

DATA

DI

AG

PRNT

F0804.EPS

Figure 8.2.1b BT200 Screen Component

Advertising