IM 01C21F01-01E

7-2

7. OPERATION

7.2 Zero Point Adjustment

Adjust the zero point after operating preparation is
completed.

IMPORTANT

Do not turn off the power to the transmitter
immediately after a zero adjustment. Powering
off within 30 seconds after a zero adjustment will
return the adjustment back to the previous
settings.

The zero point adjustment can be made in either way:
using the zero-adjustment screw of the transmitter or
the BT200 operation.

For output signal checking, display the parameter A10:
OUTPUT (%)
in the BT200.

Output signal (%)
display

PARAM
A10:OUTPUT(%)
0.0 %
A11:ENGR OUTPUT

A20:AMP TEMP

DATA

DIAG

PRNT

ESC

F0704.EPS

Zero-adjustment
screw

BT200

Zero-adjustment Screw

After reviewing this parameter you are prepared to
adjust the zero point. When making the zero adjust-
ment on a pressure transmitter, the process pressure
value does not have to be set to the low limit of the
measurement range (0%). In such case, adjust the
transmitter output signal to the actual measured value
obtained from a high-accuracy pressure measuring
instrument.

7.2.1 When you can obtain Low Range

Value from actual measured value
of 0% (0 kPa, atmospheric pres-
sure);

For pressure measurement using gauge pressure
transmitters, follow the step below before zero point
adjustment.
1) Close the tap valve (main valve).
2) Loosen the fill plug so that the pressure applied to

the transmitter is only the head of the seal liquid.

3) Adjust the zero point at this status.
4) After the adjustment, close the fill plug and then

gradually open the tap valve.

᭿ Using the Transmitter Zero-adjustment

Screw

Before adjusting a screw, check that the parameter
J20: EXT ZERO ADJ displays ENABLE. See
Subsection 8.3.3 (11) for the setting procedure.

• Use a slotted screwdriver to turn the zero-adjustment

screw. Turn the screw clockwise to increase the
output or counterclockwise to decrease the output.
The zero point adjustment can be made with a
resolution of 0.01% of the setting range. Since the
degree of zero adjustments varies with the screw
turning speed, turn the screw slowly for fine adjust-
ment and quickly for coarse adjustment.

᭿ Using the BT200
Zero point can be adjusted by simple key operation of
the BT200.

Select parameter J10: ZERO ADJ, and press the
ENTER key twice. The zero point will be adjusted
automatically to the output signal 0% (4 mA DC).
Confirm that the setting value displayed for the
parameter is ‘0.0%’ before pressing the ENTER key.
See Subsection 8.3.3 (11) for BT200 operating proce-
dures.

Display when parameter

J10 is selected.

Press

key

twice for 0% output 4 mA DC.

SET
J10:ZERO ADJ
–0.0 %
+ 000.0

CLR

ESC

F0705.EPS