2. HANDLING CAUTIONS

2.

HANDLING CAUTIONS

This chapter describes important cautions regarding
how to handle the transmitter. Read carefully before
using the transmitter.

The EJA-A Series pressure transmitters are thoroughly
tested at the factory before shipment. When the
transmitter is delivered, visually check them to make
sure that no damage occurred during shipment.

Also check that all transmitter mounting hardware
shown in Figure 2.1.1 is included. If the transmitter
was ordered without the mounting bracket, the trans-
mitter mounting hardware is not included. After
checking the transmitter, repack it in the way it was
delivered until installation.

U-bolt nut (S)

Plate

U-bolt nut (L)

U-bolt (L)

Mounting bracket
(Flat type)

F0201.EPS

Adapter

U-bolt (S)

Figure 2.1.1 Transmitter Mounting Hardware

2.1 Model and Specifications

Check

The model name and specifications are indicated on the
name plate attached to the case. If the reverse operat-
ing mode was ordered (reverse signal), ‘REVERSE’
will be inscribed in field *

1

.

F0202.EPS

: Refer to USER'S MANUAL

Figure 2.1.2 Name Plate

2.2 Unpacking

When moving the transmitter to the installation site,
keep it in its original packaging. Then, unpack the
transmitter there to avoid damage on the way.

2.3 Storage

The following precautions must be observed when
storing the instrument, especially for a long period.

(a) Select a storage area which meets the following

conditions:
• It is not exposed to rain or water.
• It suffers minimum vibration and shock.
• It has an ambient temperature and relative

humidity within the following ranges.

Ambient temperature:

–40 to 85

°C without integral indicator

–30 to 80

°C with integral indicator

Relative humidity:

5% to 100% R.H. (at 40

°C)

Preferred temperature and humidity:

approx. 25

°C and 65% R.H.

(b) When storing the transmitter, repack it as nearly

as possible to the way it was packed when
delivered from the factory.

(c) If storing a transmitter that has been used,

thoroughly clean the chambers inside the body, so
that no measured fluid remains in it. Also make
sure before storing that the transmitter assemblies
are securely mounted.

2.4 Selecting the Installation

Location

The transmitter is designed to withstand severe
environmental conditions. However, to ensure stable
and accurate operation for years, observe the follow-
ing precautions when selecting an installation loca-
tion.

(a) Ambient Temperature

Avoid locations subject to wide temperature
variations or a significant temperature gradient. If
the location is exposed to radiant heat from plant
equipments, provide adequate thermal insulation
and/or ventilation.

(b) Ambient Atmosphere

Avoid installing the transmitter in a corrosive
atmosphere. If the transmitter must be installed in
a corrosive atmosphere, there must be adequate
ventilation as well as measures to prevent
intrusion or stagnation of rain water in conduits.