2. HANDLING CAUTIONS

• EJA130A, EJA440A, EJA510A, and EJA530A can

be used above 200 bar and therefore considered as
a part of a pressure retaining vessel where category
lll, Module H applies. These models with option
code /PE3 conform to that category.

(2) Technical Data

• Models without /PE3
Article 3, Paragraph 3 of PED, denoted as Sound

Engineering Practice (SEP) .

• Models with /PE3
Module: H
Type of Equipment: Pressure Accessory - Vessel
Type of Fluid: Liquid and Gas
Group of Fluid: 1 and 2

Model

EJA110A

EJA120A

EJA130A

EJA130A

With code /PE3

EJA310A

EJA430A

EJA440A

EJA440A

With code /PE3

EJA510A

EJA510A

With code /PE3

EJA530A

EJA530A

With code /PE3

Category

*2

Article 3, paragraph 3

(SEP)

Article 3, paragraph 3

(SEP)

Article 3, paragraph 3

(SEP)

III

Article 3, paragraph 3

(SEP)

Article 3, paragraph 3

(SEP)

Article 3, paragraph 3

(SEP)

III

Article 3, paragraph 3

(SEP)

III

Article 3, paragraph 3

(SEP)

III

PS-V(bar-L)

1.6

0.005

4.2

4.2

1.6

1.6

50

50

50

50

50

50

V(L)

0.01

0.01

0.01

0.01

0.01

0.01

0.01

0.01

0.01

0.01

0.01

0.01

PS(bar)

*1

160

0.5

420

420

160

160

500

500

500

500

500

500

*1: PS is maximum allowable pressure for vessel itself.
*2: Referred to Table 1 covered by ANNEX II of EC Directive
on Pressure Equipment Directive 97/23/EC

T0299.EPS

(3) Operation

CAUTION

• The temperature and pressure of fluid should

be applied under the normal operating condi-
tion.

• The ambient temperature should be applied

under the normal operating condition.

• Please pay attention to prevent the excessive

pressure like water hammer, etc. When water
hammer is to be occurred, please take mea-
sures to prevent the pressure from exceeding
PS by setting the safety valve, etc. at the
system and the like.

• When external fire is to be occurred, please

take safety measures at the device or system
not to influence the transmitters.

2.12 Low Voltage Directive

Applicable standard : EN61010-1

(1) Pollution Degree 2

"Pollution degree" describes the degree to which a

soild, liquid, or gas which deteriorates dielectric
strength or surface resistivity is adhering. " 2 "
applies to normal indoor atmosphere. Normally,
only non-conductive pollution occurs. Occasionally,
however, temporary conductivity caused by
condenstaion must be expected.

(2) Installation Category I

"Overvoltage category(Installation category)"

describes a number which defines a transient
overvoltage condition. It implies the regulattion for
impulse withstand voltage. " I " applies to electrical
equipment which is supplied from the circuit when
appropriate transient overvoltage control means
(interfaces) are provided.