2) flameproof type, 5 grounding, 6 power supply voltage and load resistance – Yokogawa EJA530A User Manual

Page 27: 2) flameproof type -3, Grounding -3, Power supply voltage and load resistance -3

Advertising
background image

IM 01C21F01-01E

6-3

6. WIRING

(2) Flameproof Type

Wire cables through a flameproof packing adapter, or
using a flameproof metal conduit.

᭿ Wiring cable through flameproof packing adapter.
• Apply a nonhardening sealant to the terminal box

connection port and to the threads on the flameproof
packing adapter for waterproofing.

F0608.EPS

Flameproof packing adapter

Flexible metal conduit

Wiring metal

conduit

Tee

Drain plug

Apply a non-hardening
sealant to the threads for
waterproofing.

Figure 6.4.2b Typical Cable Wiring Using Flameproof

Packing Adapter

᭿ Flameproof metal conduit wiring
• A seal fitting must be installed near the terminal box

connection port for a sealed construction.

• Apply a non-hardening sealant to the threads of the

terminal box connection port, flexible metal conduit
and seal fitting for waterproofing.

F0609.EPS

Non-hazardous area

Hazardous area

Flameproof
heavy-gauge
steel conduit

Tee

Drain plug

Seal fitting

Gas sealing device

Flameproof flexible
metal conduit

Apply a non-hardening
sealant to the threads of
these fittings for
waterproofing

After wiring, impregnate the fitting
with a compound to seal tubing.

Figure 6.4.2c Typical Wiring Using Flameproof Metal

Conduit

6.5 Grounding

Grounding is always required for the proper operation
of transmitters. Follow the domestic electrical require-
ments as regulated in each country. For a transmitter
with built-in lightning protector, grounding should
satisfy ground resistance of 10

⍀ or less.

Ground terminals are located on the inside and outside
of the terminal box. Either of these terminals may be
used.

Ground terminal
(Inside)

Ground terminal
(Outside)

Transmitter terminal box

F0610.EPS

Figure 6.5 Ground Terminals

6.6 Power Supply Voltage and

Load Resistance

When configuring the loop, make sure that the external
load resistance is within the range in the figure below.

(Note) In case of an intrinsically safe transmitter, external load

resistance includes safety barrier resistance.

;;

600

250

0

10.5

16.4

24.7

42

External

load

resistance

R (

Ω)

Power supply voltage E (V DC)

F0611.EPS

Communication

applicable range

BRAIN and HART

R=

E–10.5

0.0236

Figure 6.6 Relationship between Power Supply Voltage

and External Load Resistance