IM 01C21F01-01E

10-6

10. GENERAL SPECIFICATIONS

Item

Description

Code

Painting

Color change

Coating change

Lightning protector

Calibration units

P

X1

HC

A

D1

D3

D4

(See Table for Span and

Range Limits.)

Amplifier cover only

PR

Amplifier cover and terminal cover, Munsell 7.5 R4/14

Epoxy resin-baked coating

Transmitter power supply voltage: 10.5 to 32 V DC (10.5 to 30 V DC for intrinsically safe
type, 9 to 32 V DC for F

OUNDATION

Fieldbus and PROFIBUS PA communication type.)

Allowable current: Max. 6000 A (1

ϫ40 ␮s), Repeating 1000 A (1ϫ40 ␮s) 100 times

316 SST exterior parts

Exterior parts on the amplifier housing (name plates, tag plate, zero-adjustment screw,
stopper screw) will become 316 or 316L SST.

P calibration (psi unit)

bar calibration (bar unit)

M calibration (kgf/cm

2

unit)

Oil-prohibited use

Mill Certificate

M15

Process connector

Fast response *

2

F1

Update time: 0.125 sec or less, see GS for the response time.

Stainless steel tag plate

N4

HAC

JIS SUS304 stainless steel tag plate wired onto transmitter

Stainless steel amplifier
housing

Amplifier housing material; SCS14A stainless steel (equivalent to SUS316 cast stainless
steel or ASTM CF-8M)

E1

Degrease cleansing treatment

Degrease cleansing treatment with fluorinated oil filled capsule.
Operating temperature: –20 to 80°C

K1

K2

Pressure test/
Leak test Certificate

T05

T06

T07

T08

Nitrogen (N

2

) Gas

Retention time: 10 minutes

Test Pressure: 200 kPa (2 kgf/cm

2

)

Test Pressure: 2 MPa (20 kgf/cm

2

)

Test Pressure: 10 MPa (100 kgf/cm

2

)

Test Pressure: 50 MPa (500 kgf/cm

2

)

T1008.EPS

Failure alarm down-scale *

1

C1

C2

C3

Output status at CPU failure and hardware error is –5%, 3.2 mA or less.

NAMUR NE43 compliant *

1

Output signal limits:
3.8 mA to 20.5 mA

Failure alarm down-scale: output status at CPU failure and
hardware error is –5%, 3.2 mA or less.

Failure alarm up-scale: output status at CPU failure and
hardware error is 110%, 21.6 mA or more.

High Accuracy (Applicable only for Model EJA530A)

High Accuracy type

PE3

European Pressure
Equipment Directive

PED 97/23/EC
CATEGORY: III, Module: H, Type of Equipment: Pressure Accessory - Vessel,
Type of Fluid: Liquid and Gas,
Group of Fluid: 1 and 2

*1:

Applicable for Output signal code D and E. The hardware error indicates faulty amplifier or
capsule. When combining with Optional code F1, output status for down-scale is –2.5%,
3.6 mA DC or less.

*2:

Applicable for Output signal code D and E. Write protection switch is attached for Output code E.