8. BRAIN TERMINAL BT200 OPERATION

b. Setting Calibration Range Lower

Range Value and Higher Range Value
(C21: LOW RANGE, C22: HIGH
RANGE)

These range values are set as specified in the order
before the instrument is shipped. Follow the proce-
dure below to change the range.

• The measurement span is determined by the high

and low range limit values. In this instrument,
changing the low range value also automatically
changes the high range value, keeping the span
constant.

• Example 1: With present settings of 0 to 30 kPa,

set the lower range value to 0.5 kPa.

Span = Higher range value – Lower range value

FEED

NO

OK

SET
C21:LOW RANGE
0.5 kPa

DATA

DIAG

PRNT

ESC

SET
C20:PRESS UNIT
kPa
C21:LOW RANGE
0.5 kPa
C22:HIGH RANGE
30.5 kPa

DEL

CLR

ESC

SET
C21:LOW RANGE
0 kPa
+ 0.5

The higher range value is changed

while the span remains constant.

Set 0.5.

Press the key twice to

enter the setting.

Press the (OK) key.

F0813.EPS

• Note, however, that changing the higher range value

does not cause the lower range value to change.
Thus, changing the higher range value also changes
the span.

• Calibration range can be specified with range value

specifications up to 5 digits (excluding any decimal
point) for low or high range limits within the range
of –32000 to 32000.

• Example 2: With present settings of 0 to 30 kPa,

set the Higher range value to10 kPa.

FEED

NO

OK

SET
C22:HIGH RANGE
10 kPa

DATA

DIAG

PRNT

ESC

PARAM
C20:PRESS UNIT
kPa
C21:LOW RANGE
0 kPa
C22:HIGH RANGE
10 kPa

DEL

CLR

ESC

SET
C22:HIGH RANGE
30 kPa
+ 10

The low range value is not
changed, so the span changes.

Set 10.

Press the key twice

to enter the setting.

F0814.EPS

Press the (OK) key.

(3) Damping Time Constant Setup

(C30: AMP DAMPING)

When the instrument is shipped, the damping time
constant is set at 2.0 seconds. Follow the procedure
below to change the time constant.

• Example: Change from 2.0 sec to 4.0 sec.

ESC

SET
C30:AMP DAMPING
4.0 sec

FEED

NO

OK

SET
C30:AMP DAMPING
2.0 sec
< 2.0 sec >
< 4.0 sec >
< 8.0 sec >
< 16.0 sec >

Use the or key to

select 4.0 sec.

Press the key twice to

enter the setting.

F0815.EPS

0.2sec
0.5sec
1.0sec

2.0sec

4.0sec

8.0sec
16.0sec
32.0sec
64.0sec

Press the (OK) key.

Note: The damping time constant set here is the damping time

constant for the amplifier assembly. The damping time
constant for the entire transmitter is the sum of the values for
the amplifier assembly and for the capsule assembly. For the
capsule assembly damping time constant (fixed), see the
“General Specifications” found at the end of this manual.
(See Chapter 10.)