3 iecex certification, Iecex certification -6 – Yokogawa EJA530A User Manual

Page 14

Advertising
background image

IM 01C21F01-01E

2-6

2. HANDLING CAUTIONS

• When installed in Division 2, “SEALS NOT

REQUIRED.”

Note 3. Operation

• Keep the “CAUTION” label attached to the

transmitter.

CAUTION: OPEN CIRCUIT BEFORE
REMOVING COVER.
OUVRIR LE CIRCUIT AVANT
D´NLEVER LE COUVERCLE.

• Take care not to generate mechanical sparking

when accessing to the instrument and peripheral
devices in a hazardous location.

Note 4. Maintenance and Repair

• The instrument modification or parts replacement

by other than authorized representative of
Yokogawa Electric Corporation and Yokogawa
Corporation of America is prohibited and will void
Canadian Standards Explosionproof Certification.

Non-hazardous
Location
Equipment

42 V DC Max.
4 to 20 mA DC
Signal

Non-Hazardous

Locations

Hazardous Locations Division 1

Non-Hazardous

Locations

Hazardous Locations Division 2

50 cm Max.

Sealing Fitting

Conduit

EJA Series

Non-hazardous
Location
Equipment

42 V DC Max.
4 to 20 mA DC
Signal

Sealing Fitting

EJA Series

F0205.EPS

c. CSA Intrinsically Safe Type/CSA

Explosionproof Type

Model EJA Series pressure transmitters with
optional code /CU1 can be selected the type of
protection (CSA Intrinsically Safe or CSA
Explosionproof) for use in hazardous locations.

Note 1. For the installation of this transmitter,

once a particular type of protection is
selected, any other type of protection
cannot be used. The installation must be
in accordance with the description about
the type of protection in this instruction
manual.

Note 2. In order to avoid confusion, unnecessary

marking is crossed out on the label other
than the selected type of protection when
the transmitter is installed.

2.9.3 IECEx Certification

Model EJA Series differential, gauge, and
absolute pressure transmitters with
optional code /SU2 can be selected the type of
protection (IECEx Intrinsically Safe/type n or
flameproof) for use in hazardous locations.

Note 1. For the installation of this transmitter,

once a particular type of protection is
selected, any other type of protection
cannot be used. The installation must be
in accordance with the description about
the type of protection in this instruction
manual.

Note 2. In order to avoid confusion, unnecessary

marking is crossed out on the label other
than the selected type of protection when
the transmitter is installed.

a. IECEx Intrinsically Safe Type / type n

Caution for IECEx Intrinsically safe and type n.

Note 1. Model EJA Series differential, gauge, and

absolute pressure transmitters with
optional code /SU2 are applicable for use
in hazardous locations.

• No. IECEx KEM 06.0007X
• Applicable Standard: IEC 60079-0:2004,
IEC 60079-11:1999, IEC 60079-15:2005,
IEC 60079-26:2004
• Type of Protection and Marking Code:
Ex ia IIC T4, Ex nL IIC T4
• Ambient Temperature :–40 to 60

°C

• Max. Process Temp.: 120

°C

• Enclosure: IP67

Note 2. Entity Parameters

• Intrinsically safe ratings are as follows:

Maximum Input Voltage (Ui) = 30 V
Maximum Input Current (Ii) = 165 mA
Maximum Input Power (Pi) = 0.9 W
Maximum Internal Capacitance (Ci) = 22.5 nF
Maximum Internal Inductance (Li) = 730

µH

• Type "n" ratings are as follows:

Maximum Input Voltage (Ui) = 30 V
Maximum Internal Capacitance (Ci) = 22.5 nF
Maximum Internal Inductance (Li) = 730

µH

• Installation Requirements

Uo

≤ Ui, Io ≤ Ii, Po ≤ Pi,

Co

≥ Ci + Ccable, Lo ≥ Li + Lcable

Uo, Io, Po, Co, and Lo are parameters of
barrier.

Advertising