<3. Handling Cautions>

3-10

IM 01C25R01-01E

MODEL: Specified model code.

STYLE: Style code

SUFFIX: Specified suffix code.

SUPPLY: Supply voltage (HART

Communication Type)

Supply voltage and Power (Modbus

Communication Type)

For F

OUNDATION

Fieldbus

communication type, refer to IM

01C25R03-01E.

OUTPUT: Output signal.

MWP: Maximum working pressure.

CAL RNG: Specified calibration range.

NO.: Serial number and year of production*

1

.

TOKYO 180-8750 JAPAN:

The manufacturer name and the address*

2

.

*1: The first number in the second block of “NO.” column

is the last one number of the production year.

second block

NO. 91K819857 132 7

The year 2011

*2: “180-8750” is a zip code which represents the

following address.

2-9-32 Nakacho, Musashino-shi, Tokyo Japan

*3: The identification number of Notified Body.

3.9.4 IECEx Certification

a. IECEx Flameproof Type
Caution for IECEx flameproof type.

Note 1. EJX multivariable transmitter with optional

code /SF2 are applicable for use in

hazardous locations:

• No. IECEx CSA 07.0008

• Applicable Standard: IEC60079-0:2004,

IEC60079-1:2003

• Flameproof for Zone 1, Ex d IIC T6...T4

• Enclosure: IP66 and IP67

• Maximum Process Temperature:

120°C (T4), 100°C (T5), 85°C (T6)

• Ambient Temperature: –50 to 75°C (T4),

–50 to 80°C (T5), –50 to 75°C (T6)

• Supply Voltage: 42 V dc max.

• Output Signal: 4 to 20 mA dc

Note 2. Wiring

• In hazardous locations, the cable entry

devices shall be of a certified flameproof

type, suitable for the conditions of use and

correctly installed.

• Unused apertures shall be closed with

suitable flameproof certified blanking

elements.

Note 3. Operation

• WARNING:

AFTER DE-ENERGIZING, DELAY 5

MINUTES BEFORE OPENING.

• WARNING:

WHEN AMBIENT TEMPERATURE ≥ 65°C,

USE THE HEAT-RESISTING CABLES ≥

90°C.

• Take care not to generate mechanical

sparking when accessing to the instrument

and peripheral devices in a hazardous

location.

Note 4. Maintenance and Repair

• The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void IECEx

Certification.

3.10 EMC Conformity Standards

EN61326-1 Class A, Table 2 (For use in industrial

locations)
EN61326-2-3

CAUTION

• This instrument is a Class A product,

and it is designed for use in the industrial

environment. Please use this instrument in

the industrial environment only.

• To meet EMC regulations, Yokogawa

recommends that customers run signal

wiring through metal conduits or use

shielded twisted-pair cabling when installing

EJX series transmitters in a plant.