<7. Wiring>

7-1

IM 01C25R01-01E

7. Wiring

7.1 Wiring Precautions

IMPORTANT

• The information in the sections from 7.2

throught 7.5 (except for 7.5.2) is specific to

HART protocol type. Refer to IM01C25R03-

01E for F

OUNDATION

Fieldbus protocol

type or IM 01C25R05-01EN for Modbus

Communication Type.

• Lay wiring as far as possible from electrical

noise sources such as large capacity

transformers, motors, and power supplies.

• Remove the electrical connection dust cap

before wiring.

• All threaded parts must be treated with

waterproofing sealant. (A non-hardening

silicone group sealant is recommended.)

• To prevent noise pickup, do not pass signal

and power cables through the same ducts.

• Explosion-protected instruments must

be wired in accordance with specific

requirements (and, in certain countries,

legal regulations) in order to preserve the

effectiveness of their explosion-protected

features.

• The terminal box cover is locked by an

Allen head bolt (a shrouding bolt) on ATEX

flameproof type transmitters. When the

shrouding bolt is driven clockwise using

an Allen wrench, it goes in. The cover lock

can then be released and the cover can

be opened by hand. See subsection 8.4

“Disassembly and Reassembly” for details.

• Plug and seal an unused conduit connection.

• Do not turn on power until all wirings

including RTD finished.

7.2 Selecting the Wiring

Materials

(a) Use stranded leadwires or cables which are

the same as or better than 600 V grade PVC

insulated wire or its equivalent.

(b) Use shielded wires in areas that are susceptible

to electrical noise.

(c) In areas with higher or lower ambient

temperatures, use appropriate wires or cables.

(d) In environment where oils, solvents, corrosive

gases or liquids may be present, use wires or

cables that are resistant to such substances.

(e) It is recommended that crimp-on solderless

terminal lugs (for 4 mm screws) with insulating

sleeves be used for leadwire ends.

7.3 Types of Output

Table 7.2 shows the wiring example according to

the output types.

(1) Analog Output (4 to 20 mA DC)
This instruments uses the same two wires for both,

the signal and power supply. A DC power supply is

required in a transmission loop. The total leadwire

resistance including the instrument load and power

distributor (supplied by the user) must conform to

a value in the permissible load resistance range.

Refer to Figure below.

F0701.ai

E-10.5

0.0244

(Ω)

Power supply voltage E (V DC)

600

250

R

10.5

16.6

25.2

42

External

load

resistance

Digital

Communication

range

R=

Figure 7.1

Relation between Power Supply

Voltage and Load Resistance (4 to 20

mA DC Output)

Advertising