<9. Maintenance>

9-10

IM 01C25R01-01E

9.5.3 Alarms and Countermeasures

Table 9.3

Alarm Message Summary (HART protocol type)

Integral

indicator

HART communicator

display

Cause

4-20mA Output

operation during error

Countermeasure Status

group

AL. 01

CAP.ERR

P sensor error

Sensor problem.

Outputs the signal (High or

Low) set with burnout direction

switch.

[status output: undefined]

Replace capsule if

the error recurs after

the transmitter is

restarted.

1

CT sensor error

Capsule temperature

sensor problem.

Replace capsule.

Cap EEPROM error

Capsule EEPROM

problem.

AL. 02

AMP.ERR

AT sensor error

Amplifier temperature

sensor problem.

Replace amplifier.

Amp EEPROM error Amplifier EEPROM

problem.

CPU board error

Amplifier problem.

2

AD Converter error

A/D Converter problem.

4

AL. 03

ET.ERR

ET sensor error

External temperature

sensor disconnection.

Check external

temperature sensor.

No device ID

No device ID is found.

Continues to operate and

output.

2

AL. 10

PRESS

P outside limit

Input is outside

measurement range limit of

capsule.

When PV is Pres

Output AO upper limit or AO

Lower limit.

Check input or

replace capsule when

necessary.

3

AL. 11

ST. PRSS

SP outside limit

Static pressure exceeds

limit.

When PV is SP

Output AO upper limit or AO

Lower limit.

AL. 12

CAP.TMP

CT outside limit

Capsule temperature is

outside range (–50 to

130°C).

Continues to operate and

output.

Use heat insulation or

make lagging to keep

temperature within

range.

AL. 13

AMP.TMP

AT outside limit

Amplifier temperature

is outside range (–50 to

95°C).

AL. 14

EXT. TMP

ET outside limit

External temperature is

outside range.

When PV is ET

Output AO upper limit or AO

Lower limit.

AL. 15

EXT. TMP

OHM outside limit

External temperature

sensor resistance is out

specification.

AL. 16 PLS PLS outside limit

Pulse output is out

specification.

Continues to operate and

output.

Check settings and

change them.

AL. 30

PRS.RNG

P over range

Differential pressure

exceeds specified range.

When PV is Pres.

Outputs the signal (High or

Low) set with burnout direction

switch.

Low:–1.25%, High:110%

Check input and

range setting, and

change them as

needed.

AL. 31

SP. RNG

SP over range

Static pressure exceeds

specified range.

When PV is SP

Outputs the signal (High or

Low) set with burnout direction

switch.

Low:–1.25%, High:110%

4

AL. 32

F. RNG

F over range

Flow exceeds specified

range.

When PV is Flow

Outputs the signal (High or

Low) set with burnout direction

switch.

Low:–1.25%, High:110%

AL. 33

ET. RNG

ET over range

External temperature

exceeds specified range.

When PV is ET

Outputs the signal (High or

Low) set with burnout direction

switch.

Low:–1.25%, High:110%