5 cable connection rtd terminal box side, Removing shielded cable with cable gland, Removing shielded cable for conduit use – Yokogawa EJX930A User Manual

Page 45: External temperature input code: -b, -c, -d) -8, Cable connection rtd terminal box side -8, Caution

Advertising
background image

<7. Wiring>

7-8

IM 01C25R01-01E

7.6.3 Removing Shielded Cable with Cable

Gland (External temperature input

code: -1, -2, -3, and -4)

(1) By pulling out the string attached to the

connector, carefully unplug the connector from

the transmitter’s connecting port.

(2) In the case of using 1/2NPT Type or M20

Type cable gland, remove the running coupler

and backnut assembly by turning the running

coupler.

In the case of using G1/2 Type cable gland,

loosen the lock nut screwed into the union

cover and remove the union cover. RTD cable

can be pulled out together with the packing box.

Loosen the clamp nut and the gland if

necessary.

(3) Pull the RTD cable out carefully.

(4) In the case of 1/2NPT Type or M20 Type cable

gland, remove the entry from the RTD electrical

connection by turning the entry.

In the case of G1/2 Type cable gland, loosen

the lock nut screwed into the adapter body and

remove the adapter body.

NOTE

In the case of G1/2 Type cable gland, remove

the rubber packing, washer, gland, clamp ring,

clamp nut, union coupling and union cover from

the opposite side of RTD connector in order to

take out the cable gland from the RTD cable.

7.6.4 Removing Shielded Cable for

Conduit Use (External temperature

input code: -B, -C, -D)

(1) By pulling out the string attached to the

connector, slowly unplug the connector from the

transmitter's connecting port.

(2) Remove the conduit from the RTD electrical

connection.

(3) Pull the RTD cable out through the RTD

electrical connection.

7.6.5 Cable Connection RTD Terminal Box

Side

EJX multivariable transmitter RTD I/F is for 3-wire

Type RTD, Pt100.
Heed the following when wiring an RTD of the 2- or

4-wire type.

NOTE

Please note that a temperature error will occur

when you use a 2-wire RTD because of wiring

resistance.

Please do not ground the shield on the RTD side

of the cable.

CAUTION

Please use only the cables provided with this

instrument.

When wiring, be sure not to damage the cable's

insulation or its core.

All the cable cores must have sufficient insulation

around them.

Do not let the signal line contact the shield line.

Do not allow the shield line or the signal line to

come the earth potential voltage.

2-Wire

3-Wire

4-Wire

A

B A

B b A

B b

a

F0723.ai

Figure 7.11 The Method of Wiring for the RTD Side

Table 7.1

The Method of Wiring for the RTD Side

RTD Terminal

RTD

Terminal

A

a

B

b

2-Wire

White

Blue1 and Blue2

3-Wire

White

Blue1

Blue2

4-Wire

White

open

Blue1

Blue2

NOTE

The color display in the table shows the white

line of the cable.

The cable color could change depending on the

cable type.

Blue1 and blue2 allow changing places.

For 2-wire Type, connect either which is blue1 or

blue2, and give other side as OPEN.

Advertising