<7. Wiring>

7-9

IM 01C25R01-01E

7.7 Grounding

Grounding is always required for the proper

operation of transmitters. Follow the domestic

electrical requirements as regulated in each

country. For a transmitter with a built-in lightning

protector, grounding should satisfy ground

resistance of 10Ω or less.
Ground terminals are located on the inside and

outside of the terminal box. Either of these terminals

may be used.

F0724.ai

Ground terminal

(inside)

Ground terminal

(outside)

SUPPL

Y

PULSE

CHECK

ALARM

Figure 7.12 Ground Terminals (Eg. HART

Communication Type)