<3. Handling Cautions>

3-11

IM 01C25R01-01E

3.11 Pressure Equipment

Directive (PED)

(1) General

• EJX series pressure transmitters are

categorized as piping under the pressure

accessories section of directive 97/23/EC,

which corresponds to Article 3, Paragraph 3 of

PED, denoted as Sound Engineering Practice

(SEP).

• EJX910A-M, EJX910A-H, EJX930A-M,

and EJX930A-H can be used above 200

bar and therefore considered as a part of a

pressure retaining vessel where category III,

Module H applies. These models with option

code /PE3 conform to that category.

(2) Technical Data

• Models without /PE3

Article 3, Paragraph 3 of PED, denoted as

Sound Engineering Practice (SEP).

• Models with /PE3

Module: H

Type of Equipmen: Pressure Accessory-Vessel

Type of fluid: Liquid and Gas

Group of fluid: 1 and 2

Model

Capsule

code

PS*

1

(bar) V(L)

PS.V

(bar.L) Category

*

2

EJX910A

L

160 0.01

1.6

Article 3,

Paragraph 3

(SEP)

M, H

250 0.01

2.5

EJX910A

with code

/PE3

M, H

250 0.01

2.5

III

EJX930A

M, H

500 0.01

5.0

Article 3,

Paragraph 3

(SEP)

EJX930A

with code

/PE3

M, H

500 0.01

5.0

III

*1:

PS is maximum pressure for vessel itself based on

Pressure Equipment Directive 97/23/EC.

Refer to General specification for maximum working

pressure of a transmitter.

*2:

Referred to Table 1 covered by ANNEX II of EC Directive

on Pressure Equipment Directive 97/23/EC

(3) Operation

CAUTION

• The temperature and pressure of fluid should

be maintained at levels that are consistent

with normal operating conditions.

• The ambient temperature should be

maintained at a level that is consistent with

normal operating conditions.

• Please take care to prevent water hammer

and the like from inducing excessive

pressures in pipes and valves. If phenomena

are likely, install a safety valve or take

some other appropriate measure to prevent

pressure from exceeding PS.

• Take appropriate measures at the device or

system level to protect transmitters if they

are to be operated near an external heat

source.

3.12 Low Voltage Directive

Applicable standard: EN61010-1

(1) Pollution Degree 2

“Pollution degree” describes the degree to

which a solid, liquid, or gas which deteriorates

dielectric strength or surface resistivity

is adhering. “2” applies to normal indoor

atmosphere. Normally, only non-conductive

pollution occurs. Occasionally, however,

temporary conductivity caused by condensation

must be expected.

(2) Installation Category I

“Overvoltage category (Installation category)”

describes a number which defines a transient

overvoltage condition. It implies the regulation

for impulse withstand voltage. “ I ” applies to

electrical equipment which is supplied from the

circuit when appropriate transient overvoltage

control means (interfaces) are provided.