8.5.1 Draining Condensate

1) Gradually open the drain screw or drain plug

and drain the transmitter pressure-detector

section. (See figure 8.4)

2) When all accumulated liquid is completely

removed, close the drain screw or drain plug.

3) Tighten the drain screw to a torque of 10 N·m,

and the drain plug to a torque of 34 to 39 N·m.

F0805.ai

When you loosen the drain screw or drain

plug, the accumulated liquid will be expelled

in the direction of the arrow.

Drain screw

Drain plug

Figure 8.4

Draining the Transmitter

8.5.2 Venting Gas

1) Gradually open the vent screw to vent gas from

the transmitter pressure-detector section. (See

figure 8.5)

2) When the transmitter is completely vented,

close the vent screw.

3) Tighten the vent screw to a torque of 10 N·m.

F0806.ai

When you loosen the vent screw, the gas

escapes in the direction of the arrow.

Vent screw

Vent screw

Figure 8.5

Venting the Transmitter