2 zero point adjustment, 1 adjusting zero point for differential pressure, Zero point adjustment -2 8.2.1 – Yokogawa EJX930A User Manual

Page 49: Adjusting zero point for differential pressure -2, Important

Advertising
background image

<8. Operation>

8-2

IM 01C25R01-01E

■ Confirming that Transmitter is Operating

Properly

Using the HART communicator

• If the wiring system is faulty, ‘No device found at

adress O Poll' or communication error’ appears

on the display.

• If the transmitter is faulty, ‘error message’

appears on the display.

Using the integral indicator

• If the wiring system is faulty, the display stays

blank.

• If the transmitter is faulty, an error code is

displayed.

Self-diagnostic error on the integral indicator

(Faulty transmitter)

F0802.ai

Figure 8.2

Integral Indicator with Error Code

NOTE

If any of the above errors are indicated on

the display of the integral indicator or the

communicator, refer to subsection 9.5.2 for the

corrective action.

■ Verify and Change Transmitter Parameter

Setting and Values

The parameters related to the following items are

set at factory as specified in order.

• Calibration range

• Software damping (optional)

Other parameters like following are shipped with the

default setting.

• Low-cut

• Process alarm setting

• Write protection

To confirm or change the values, see

IM 01C25R02-01E or 01C25R03-01E.

8.2 Zero Point Adjustment

After completing preparations for operating the

transmitter, adjust the zero point.
Zero point adjustment can be done by turning the

transmitter’s zero-adjustment screw or by using

the communicator. This section describes the

procedure for the zero-adjustment screw. For the

communicator procedure, see the communication

manual.

IMPORTANT

Do not turn off the power to the transmitter

immediately after performing a zero point

adjustment. Powering off within 30 seconds of

performing this procedure will return the zero

point to its previous setting.

NOTE

Before performing this adjustment, make sure

that the external zero adjustment function has

been enabled by a parameter setting.

External zero adjustment function only to the

differencial pressure signal.

To check the output signal, use a digital multimeter,

calibrator, or communicator.

8.2.1 Adjusting Zero Point for Differential

Pressure

Before adjusting zero point, make sure that the

equalizing valve is open.

F0803.ai

Zero-adjustment

screw cover

Figure 8.3

External Zero Adjustment Screw