<2. Notes on Handling>

2-4

IM 01C50B01-01E

a) CSA Intrinsically Safe Type/Non-incendive

Type

Caution for CSA Intrinsically safe type. (Following

contents refers “DOC No. ICS008-A13 P.1-1 and

P.1- 2”)

Note 1. Model YTA110/CU1, YTA310/CU1 and

YTA320/CU1 temperature transmitters are

applicable for use in hazardous locations:

Certificate 172608-0001053837

[For CSA C22.2]

• Applicable Standard: C22.2 No.0,

C22.2 No.0.4, C22.2 No.25, C22.2 No.94,

C22.2 No.142, C22.2 No.157, C22.2 No.213

• Intrinsically Safe for Class I, II, III, Division 1,

Groups A, B, C, D, E, F & G.

• Non-incendive for Class I, II, Division 2, Groups

A, B, C, D, F & G, Class III, Division 1.

• Encl. “Type 4X”

• Temperature Class: T4

• Ambient temperature: –40 to 60°C

Note 2. Entity Parameters (Electrical/Nonincendive

field wiring parameters)

• [Supply Circuit]

Vmax = 30 V, Imax = 165 mA, Pmax = 0.9 W,

Ci = 18 nF, Li = 730 μH

• [Associated apparatus]

Voc ≤ 30 V, Isc ≤ 165 mA, Pmax ≤ 0.9 W

• [Sensor Circuit]

Voc = 9 V, Isc = 40 mA, Po = 90 mW,

Ca = 1 μF, La = 10 mH

Note 3. Installation

• All wiring shall comply with Canadian Electrical

Code Part I and Local Electrical Codes.

• For the sensor circuitry, the above parameters

for sensor circuit must be taken into account.

• Dust-tight conduit seal must be used when

installed in class II and III environments.

• In any used safety barrier, output current must

be limited by a resistor 'R' such that Isc=Voc/R.

• The safety barrier must be CSA certified, and

the input voltage of the barrier must be less

than 250Vrms/Vdc.

• For non-incendive type, general purpose

equipment must be CSA certified and the

equipment which have non-incendive field

wiring parameters.

• The instrument modification or parts replacement

by other than authorized representative of

Yokogawa Electric Corporation is prohibited

and will void Canadian Standards Intrinsically

safe and nonincendive Certification.

F0203.ai

Safety Barrier

Supply

Hazardous Location

Nonhazardous Location

General

Purpose

Equipment

+

+

+

Supply

+

+

[Intrinsically Safe]

Hazardous Location

Nonhazardous Location

Not Use

Safety Barrier

+

[Non-incendive]

General

Purpose

Equipment

Sensor

1
2
3
4
5

Sensor

1
2
3
4
5

YTA Series

Temperature

Transmitter

YTA Series

Temperature

Transmitter

b) CSA Explosionproof Type
Caution for CSA Explosionproof type

Note 1. Model YTA110/CU1, YTA310/CU1 and

YTA320/CU1 temperature transmitters are

applicable for use in hazardous locations:

Certificate 1089576

[For CSA C22.2]

• Applicable Standard: C22.2 No.0,

C22.2 No.0.4, C22.2 No.25, C22.2 No.30,

C22.2 No.94, C22.2 No.142, C22.2 No.157,

C22.2 No.213, C22.2 No.1010.1

• Explosionproof for Class I, Division 1, Groups

B, C and D.

• Dust-ignitionproof for Class II, Groups E, F and

G, Class III.

• Encl “Type 4X”

• Temperature Class: T6

• Ambient Temperature: –40 to 60°C

• Supply Voltage: 42 V dc max.

• Output Signal: 4 to 20 mA

Note 2. Wiring

• All wiring shall comply with Canadian Electrical

Code Part I and Local Electrical Codes.

• In hazardous location, wiring shall be in conduit

as shown in the figure.

WARNING: A SEAL SHALL BE INSTALLED

WITHIN 50 cm OF THE

ENCLOSURE. UN SCELLEMENT

DOIT ÊTRE INSTALLÉ À MOINS

DE 50 cm DU BOÎTIER.