Yokogawa YTA320 User Manual

Page 22

Advertising
background image

<3. Part Names and Functions>

3-3

IM 01C50B01-01E

For a list of error codes, refer to “Error code table” in

Section 6.4.
(6) Unit display
The unit specified as the unit of process in the

process variable display column in Item (5) is lit.

The output display is fixed to mA or %.

(7) Display of sensor type and number of wire

connections

Displays process variable/output items, the number

of sensor wiring connections and the multidrop

address in dot matrix (only applies to HART

communication). In the event of hardware error,

“FAIL” is displayed.
Process variable: To display the process variable

value in the process variable display in Item

(5), display the type of applicable process

variable (“PV”, “SV”, “TV”).

Output display: To display the output value in the

process variable display in Item (5), display

“OUT”. During the output of sensor burnout,

“Abn” and “OUT” are alternately dis played.

WIRE: Displays the number of wiring connections.

There are two wiring connections for

thermocouple input, while there are two to

four connections for thermometer resistor;

these are displayed alternately with the

sensor type.

The display can be hidden by setting an

applicable parameter. Note that the DIF and

AVG display does not allow the sensor type

to be displayed.

TYPE: Displays the type of sensor. Note that the

DIF and AVG display does not allow the

sensor type to be displayed. If the sensor is

customordered, “Z1” and “Z2” are displayed.

Multidrop address: If the multidrop address is 1

through 15 in HART communication, the

output display brings up these addresses

instead of display ing “OUT”.

Upon shipment from the factory, the indicator is set

as follows.

Table 3.2

Setting of Indicator upon Shipment

from the Factory

Display location

Contents

Output bar chart display

Output bar chart display

is on.

Input display

Sns1 is lit.

Process variable display

PV value and output

value (mA) are alternately

displayed.

Unit display

The unit specified upon

shipped from factory and

mA are lit.

Display of sensor type

and number of wire

connections

“PV” and “OUT” are

displayed alternately.