<2. Notes on Handling>

2-9

IM 01C50B01-01E

For example, the production year of the product engraved

in “NO.” column on the name plate as follows is 2006.

The year 2006

C2F616294

*2: “180-8750” is a postal code which represents the following

address.

2-9-32 Nakacho, Musashino-shi, Tokyo Japan

*3: The identification number of Notified Body

2.7.3 FM Certification

a) FM Intrinsically Safe Type
Caution for FM Intrinsically safe type.

Note 1. Model YTA /FU1 temperature transmitter is

applicable for use in hazardous locations.

• Applicable Standard: FM 3600, FM 3610,

FM 3611, FM 3810, NEMA-250

• Intrinsically Safe for Class I, Division 1, Groups

A, B, C & D.

Class II, Division 1, Groups E, F & G and Class

III, Division 1 Hazardous Locations.

• Outdoor hazardous locations, NEMA 4X.

• Temperature Class: T4

• Ambient temperature: –40 to 60°C

Note 2. Entity Parameters of the temperature

transmitter:

• Supply Circuit (+ and –) • Sensor Circuit (1 to 5)

Vmax : 30 V

Voc/Vt : 9 V

Imax : 165 mA

Isc/It : 40 mA

Pmax : 0.9 W

Po : 0.09 W

Ci : 18 nF

Ca : 1 μF

Li : 730 μH

La : 10 mH

• For the sensor input circuitry, these entity

parameters must be taken into account when

installed.

• Installation Requirements between temperature

transmitter and safety barrier:

Voc ≤ Vmax, Isc ≤ Imax, Ca ≥ Ci + Ccable, La ≥

Li + Lcable

Voc, Isc, Ca and La are parameters of the

safety barrier.

Note 3. Installation

• The safety barrier must be FM approved.

• Input voltage of the safety barrier must be less

than 250 Vrms/Vdc.

• Installation should be in accordance with ANSI/

ISA RP12.6 “Installation of Intrinsically Safe

Systems for Hazardous (Classified) Locations”

and the National Electric Code (ANSI/NFPA

70).

• Intrinsically safe sensor must be FMRC

Approved or be simple apparatus (a device

which will neither generate nor store more than

1.2 V, 0.1 A, 25 mW or 20 μJ, ex. switches,

thermocouples, LED’s or RTD’s).

• Dust-tight conduit seal must be used when

installed in a Class II and III environments.

Note 4. Maintenance and Repair

• The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void Factory

Mutual Intrinsically safe and Nonincendive

Approval.

F0209.ai

Class I, II, III, Division 1,

Groups A, B, C, D, E, F and G

Temperature

Transmitter

Safety Barrier

Hazardous

Location

Nonhazardous

Location

General

Purpose

Equipment

+

+ –

+

C

+

[Intrinsically Safe]

Supply

1

2

3

4

5

Sensor

Intrinsically

Safe Sensor

or Simple

Apparatus

b) FM Non-incendive Type
Caution for FM Non-incendive type.

Note 1. Model YTA /FU1 temperature transmitter is

applicable for use in hazardous locations.

• Applicable Standard: FM 3600, FM 3610,

FM 3611, FM 3810, NEMA-250

• Non-incendive for Class I, Division 2, Groups A,

B, C & D.

Class II, Division 2, Groups F & G and Class III,

Division 1 Hazardous Locations.

• Outdoor hazardous locations, NEMA 4X.

• Temperature Class: T4

• Ambient temperature: –40 to 60°C

Note 2. Non-incendive field wiring Parameters of

the temperature transmitter:

• Supply Circuit (+ and -) • Sensor Circuit (1 to 5)

Vmax : 30 V

Voc/Vt : 9 V

Imax : 165 mA

Isc/It : 40 mA

Pmax : 0.9 W

Po : 0.09 W

Ci : 18 nF

Ca : 1 μF

Li : 730 μH

La : 10 mH