Terminals – Yokogawa YTA320 User Manual

Page 38

Advertising
background image

<7. General Specifications>

7-4

IM 01C50B01-01E

Table 7.3

YTA30, YTA320 Effect of Ambient Temperature

Sensor Type

Input Range

A/D Coefficient

D/A Coeffieicient

°C

°F

T/C

B

100

300

1000

to

to

to

300

1000

1820

212

572

1832

to

to

to

572

1832

3308

± ( 0.530°C - 0.080 % of reading)

± ( 0.350°C - 0.021 % of reading )

± ( 0.140°C)

± {0.0088% of span + 0.007%

of (reading - LRV)}

E

-200 to

1000

-328 to

1832 ± ( 0.035°C + 0.042 % of abs.reading)

J

-200

0

to

to

0

1200

-328

32

to

to

32

2192

± ( 0.039°C + 0.020 % of abs.reading)

± ( 0.039°C + 0.0029 % of reading)

K

-200

0

to

to

0

1372

-328

32

to

to

32

2502

± ( 0.046°C + 0.020 % of abs.reading)

± ( 0.046°C + 0.0054 % of reading)

N

-200

0

to

to

0

1300

-328

32

to

to

32

2372

± ( 0.054°C + 0.010 % of abs.reading)

± ( 0.054°C + 0.0036 % of reading)

R

-50

200

to

to

200

1768

-58

392

to

to

392

3214

± ( 0.210°C - 0.032 % of abs.reading)

± ( 0.150°C)

S

-50

200

to

to

200

1768

-58

392

to

to

392

3214

± ( 0.210°C - 0.032 % of abs.reading)

± ( 0.150°C)

T

-200

0

to

to

0

400

-328

32

to

to

32

752

± ( 0.046°C - 0.036 % of abs.reading)

± ( 0.046°C)

W3

0

1400

to

to

1400

2300

32

2552

to

to

2552

4172

± ( 0.100°C + 0.0040 % of reading)

± ( -0.130°C + 0.020 % of reading)

W5

0

1400

to

to

1400

2300

32

2552

to

to

2552

4172

± ( 0.100°C + 0.0040 % of reading)

± ( -0.120°C + 0.020 % of reading)

L

-200

0

to

to

0

900

-328

32

to

to

32

1652

± ( 0.039°C + 0.020 % of abs.reading)

± ( 0.039°C + 0.0029 % of reading)

U

-200

0

to

to

0

600

-328

32

to

to

32

1112

± ( 0.046°C + 0.036 % of abs.reading)

± ( 0.046°C)

RTD

Pt100

Pt200

Pt500

JPt100

Cu

-200

-200

-200

-200

-70

to

to

to

to

to

850

850

850

500

150

-328

-328

-328

-328

-94

to

to

to

to

to

1562

1562

1562

932

302

± ( 0.047°C + 0.009 % of reading)

± ( 0.065°C + 0.012 % of reading)

± ( 0.047°C + 0.009 % of reading)

± ( 0.047°C + 0.009 % of reading)

± ( 0.320°C + 0.120 % of reading)

Ni120

-70 to

320

-94 to

608 ± ( 0.016°C + 0.007 % of reading)

mV

± (0.001mV + 0.0043 % of abs.reading)

ohm

± ( 0.040Ω + 0.0088 % of reading)

Note: Temperature Effect = A/D coeffieicnt + D/A coefficient (The data in the table is the coeffcient per 10°C change.)

Example 1; Pt100Ω, 0 to 200°C calibration range, 50°C reading

(0.047°C + 50°C × 0.009%) + [200°C Ч 0.0088% + (50 - 0) Ч 0.007%]

= (0.047°C + 0.0045°C) + (0.0176°C + 0.0035°C )

= ± 0.0726°C [ per 10°C change ]

Example 2; T T/C, -100 to 100°C calibration range, 250°C reading

(0.046°C + | 250°C | × 0.036%) + {200°C Ч 0.0088% + [250 - (-100)] Ч 0.007%}

= (0.046°C + 0.018°C) + (0.0176°C + 0.0035°C )

= ± 0.0851°C [ per 10°C change ]

Terminals

F0702.ai

Power Supply and output terminal

External Indicator (ammeter) terminal

*1

Ground terminal

Terminal Configuration

Communication

Terminals (BT200 etc.)

Connection hook

CHECK METER

Connection hook

*1

*1: When using an external indicator or check meter,

the internal resistance must be 10Ω or less.

The hook is not available for Fieldbus

communication type(output signal code F).

M10×1.5 12-deep female