<2. Notes on Handling>

2-7

IM 01C50B01-01E

• Ambient Temperature for Dust Atmospheres:

–40 to 65°C (T70°C), –40 to 80°C (T90°C)

• Enclosure: IP67

Note 2. Electrical Data

• Supply voltage: 42 V dc max.

• Output signal: 4 to 20 mA

Note 3. Installation

• All wiring shall comply with local installation

requirement.

• The cable entry devices shall be of a certified

flameproof type, suitable for the conditions of

use.

Note 4. Operation

• Keep strictly the “WARNING” on the label on

the transmitter.

WARNING: AFTER DE-ENERGIZING, DELAY

5 MINUTES BEFORE OPENING.

WHEN THE AMBIENT TEMP. ≥

70°C, USE THE HEATRESISTING

CABLES OF HIGHER THAN

90°C.

• Take care not to generate mechanical spark

when access to the instrument and peripheral

devices in hazardous location.

Note 5. Maintenance and Repair

• The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void ATEX

Flameproof Certification.

c) ATEX Intrinsically Safe “ic”

WARNING

When using a power supply not having a non-

incendive circuit, please pay attention not to

ignite in the surrounding flammable atmosphere.

In such a case, we recommend using wiring

metal conduit in order to prevent the ignition.

Caution for ATEX Intrinsically Safe “ic”

Note 1. Model YTA110/KU2, YTA310/KU2 and

YTA320/KU2 temperature transmitters for

potentially explosive atmospheres:

• Applicable standard: EN 60079-0:2009,

EN 60079-0:2012, EN 60079-11:2012

• Type of Protection and Marking:

II 3 G Ex ic IIC T5…T4 Gc

• Ambient Temperature: –30 to 50°C for T5,

–30 to 70°C for T4

• IP Code: IP67

• Overvoltage Category: I

Note 2. Electrical Data

• [Supply circuit]

Ui = 30 V

Effective internal capacitance, Ci = 28 nF

Effective internal inductance, Li = 730 μH

• [Sensor circuit]

Uo= 9 V Io = 40 mA Po = 90 mW

Max. allowed external capacitance, Co = 0.7 μF

Max. allowed external inductance, Lo = 10 mH

• The above parameters apply when one of the

two conditions below is given:

- the total Li of the external circuit (excluding

the cable) is < 1% of the Lo value or

- the total Ci of the external circuit (excluding

the cable) is < 1% of the Co value.

• The above parameters are reduced to 50%

when both of the two conditions below are

given:

- the total Li of the external circuit (excluding

the cable) is ≥ 1% of the Lo value and

- the total Ci of the external circuit (excluding

the cable) is ≥ 1% of the Co value.

• The reduced capacitance of the external circuit

(including cable) shall not be greater than 1μF

for Group IIB and 600nF for Group IIC.

Note 3. Installation

• All wiring shall comply with local installation

requirements. (refer to the installation diagram)

• Cable glands, adapters and/or blanking

elements shall be of Ex “n”, Ex “e” or Ex “d” and

shall be installed so as to maintain the specified

degree of protection (IP code) of the equipment.

Note 4. Operation

• Keep strictly the “WARNING” on the label on

the transmitter.

WARNING: POTENTIAL ELECTROSTATIC

CHARGING HAZARD - SEE USER’S MANUAL

Note 5. Maintenance and Repair

• The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void ATEX

Intrinsically Safe “ic“.

Note 6. Specific Conditions of Use

• Precautions shall be taken to minimize the risk

from electrostatic discharge of painted parts.

• The dielectric strength of at least 500 V a.c.

r.m.s between the intrinsically safe circuits

and the enclosure of the Model YTA series

temperature transmitter is limited only by the

overvoltage protection.