<5. Wiring>

5-5

IM 01C50B01-01E

Adapter body

Rubber packing

Washer

Packing box

Grand

Clamp ring

Clamp nut

Union coupling

Union cover

O-ring

Lock nut

Lock nut

Cable

Be sure to apply

non-hardening sealant to the

threads for water proofing.

F0512.ai

CAUTION

Figure 5.12 Flameproof Gland Packing Adapter

lnstallation

■ Flameproof metal conduit wiring

• A seal fitting must be installed near the terminal

box connection port for a sealed construction.

• Apply a nonhardening sealant to the threads of

the terminal box connection port, flexible metal

conduit and seal fitting for waterproofing.

F0513.ai

Non-hazardous

area

Hazardous

area

Flameproof

heavy-gauge

steel conduit

Tee

Drain plug

Gas sealing

device

Flameproof flexible

metal conduit

Apply a nonhardening

sealant to the threads of

these fittings for

waterproofing

Seal fitting

After wiring, impregnate the fitting

with a compound to seal tubing.

Figure 5.3 Typical Wiring Using Flameproof Metal

Conduit

5.6 Grounding

Grounding is always required for the proper

operation of transmitters. Follow the domestic

electrical requirements as regulated in each

country. For a transmitter with built-in lightning

protector, grounding should satisfy ground

resistance of 10Ω or less.
Ground terminals are located on the inside and

outside of the terminal box. Either of these terminals

may be used.

WARNING

For TIIS flameproof type and intrinsically safe,

grounding should satisfy Class D requirements

(grounding resistance, 100Ω or less).

F0514.ai

Grounding

terminal

(Inside)

Grounding

terminal

(Outside)

Figure 5.4 Grounding Terminal