MACROTEST

5035

EN - 19

4.3. RCD RCD

: TESTS ON RCDS TYPE A OR AC

The test is effected according to EN 61557-6, EN61008, EN61009, EN60947-2 B 4.2.4
and VDE 0413 part 6.

CAUTION

The automatic check of the RCD features causes the tripping of the RCD itself.
Therefore

check that there is no power or load connected downstream the

RCD under test which could be affected by the installation switching off.
Possibly disconnect all the loads connected downstream the RCD as they could
add other leakage currents to the existing ones so making the test results void.

Turn the

switch on RCD

(RCDS type A sensitive to pulsating

leakage current) or RCD

(RCDS type AC sensitive to sine leakage

current) position.

Switch on the instrument.

The key

FUNC permits to select one of the following measuring modes

(which can be shown cyclically when pressing the key):

Mode

MAN x ½ (the instrument effects the test with a leakage current

equal to half the value of the rated current set with a leakage current in
phase with the voltage or a leakage current phase shifted by 180° with
respect to the voltage).

Mode

MAN x 1 (the instrument effects the test with a leakage current

equal to once the value of the rated current set with a leakage current in
phase with the voltage or a leakage current phase shifted by 180° with
respect to the voltage).

Mode

MAN x 2 (the instrument effects the test with a leakage current

equal to twice the value of the rated current set with a leakage current in
phase with the voltage or a leakage current phase shifted by 180° with
respect to the voltage).

Mode

MAN x 5 (the instrument effects the test with a leakage current

equal to five times the value of the rated current set with a leakage
current in phase with the voltage or a leakage current phase shifted by
180° with respect to the voltage)

Mode

AUTO (the instrument effects the test automatically with a leakage

current equal to half, once, five times the value of the rated current set
with a leakage current in phase with the voltage or a leakage current
phase shifted by 180° with respect to the voltage). Recommended test.

Mode

RAMP

(the instrument effects the test with a ramp growing

leakage current, with a leakage current in phase with the voltage or with
a leakage current phase shifted by 180° with respect to the voltage. Use
this test to measure the tripping current)

Mode

U

t

(the instrument effects the test with a leakage current equal to

half the value of the selected rated current and calculates the contact
voltage as well as the R

a

earth resistance with a leakage current in phase

with the voltage or a leakage current phase shifted by 180° with respect
to the voltage).

FUNC