HT instruments MACROTEST 5035 User Manual

Page 25

Advertising
background image

MACROTEST

5035

EN - 24

NOTE: ”Man 5 I

∆n

” and “AUTO” test modes aren’t available for RCD type A

500mA.


At the end of the test if

all six tests resulted to
be positive
, the
instrument displays the
screen alongside
relative to the last
measurement effected.

RCD

~

23

ms

OK

Ι

N

30

m

A

1

V

x5

t

AUTO

180° U

L

=

50V



5. Press

the

DISP key to scroll the results relative to the six tests

effected which can be shown cyclically according to the following
order: ½I

∆n

at 0°, ½I

∆n

at 180°, I

∆n

at 0°, I

∆n

at 180°, 5I

∆n

at 0°, 5I

∆n

at

180°.

SAVING:

The test can be stored pressing the

SAVE key twice

(according to paragraph 5.1).


4.3.1.4. Mode

"RAMP "


4.

Press the

START/STOP key once. The instrument carries out the

test injecting a current in phase with positive half wave of the
voltage indicated on

display by 0°.

Press the

START/STOP key once. The instrument carries out the

test injecting a current in phase with negative half wave of the
voltage indicated on

display by 180°.

The instrument generates a leakage current growing step by step
for a given time interval.


At the end of the test if the RCD tripping

current is

≤ I

∆n

(Type AC) or 1.4I

∆n

(Type

A with I

∆n

> 10mA) or 2I

∆n

(Type A with

I

∆n

≤ 10mA), the instrument emits a

double sound signal indicating the
positive outcome of the test and
displays the screen alongside.

RCD

~

24

mA

OK

41

m

s 1 V

t

U

L

= 50 V


SAVING:

The test can be stored pressing the

SAVE key twice

(according to paragraph 5.1).

OK: indicates that the RCD
passed the test.

Value of contact
voltage

U

t

detected referred
to the rated value
of the RCD
current set.

SAVE

SAVE

or RCD

RCD tripping time

OK: indicates that
the RCD passed
the test.

Value of contact voltage

U

t

detected referred to the

rated value of the RCD current set.

or RCD

START

STOP

DISP

Advertising