4.3.3. Anomalous cases which may occur during the RCD tests in any working

mode

Should the instrument detect that the

phase and/or neutral cables are not
connected to an installation, screen
alongside is displayed when pressing
START/STOP.

RCD

~

o

P-N

VOL AG

Should the instrument detect a voltage

between phase and neutral higher of
265V, for example in case the blue
cable is connected to an installation
phase conductor of a 400V three-phase
system, the screen alongside is
displayed.

RCD

~

o

Hi

P-N

VOL AG

This screen is displayed when the phase

conductor was reversed with respect to
the neutral one.

RCD

~

o A

P-N

This screen is displayed when the

phase conductor was reversed with
respect to the earth one.

RCD

~

o A

P-PE

This screen is displayed when in

biphase system the blue conductor was
reversed with respect to the green one.

RCD

~

o A

PEN


THE PREVIOUS RESULTS CANNOT BE SAVED.


Message

“no VOL tAGE”: a too low voltage was

detected

Message

"Att":

voltage between
phase and earth
is too low.

The instrument does not effect the test.
Reverse the shuko plug or exchange the black
cable with the blue one. Repeat the test.

Message

"Att":

voltage between
phase and earth
is too low.

The instrument does not effect the test.
Reverse the phase to earth connection in the plug
or exchange the black cable with the green one.

Message

“Hi VOL tAG”:
a too high voltage
was detected.

The instrument does not effect the test.

or RCD

or RCD

or RCD

or RCD

SAVE

or RCD