Caution – HT instruments MACROTEST 5035 User Manual

Page 35

Advertising
background image

MACROTEST

5035

EN - 34


5.

Press the

START/STOP key once. The instrument carries out the

test injecting a current in phase with positive half wave of the
voltage indicated on

display by 0°.

Press the

START/STOP key twice. The instrument carries out the

test injecting a current in phase with negative half wave of the
voltage indicated on

display by 180°.

At the end of the test the instrument

emits a

double sound signal

indicating that the test is correctly
terminated
and displays the values
alongside.

LOOP

3.65

P-PE

221

V

63

A


CAUTION

The measurement of Phase-PE impedance entails the following of a current
of about 6A between the above said conductors. This may cause the tripping
of magnetothermal RCDs with nominal current value lower. If necessary
effect the test upstream the RCD itself.


Formula for calculation of prospective short circuit current:

PE

N

CC

Z

U

I

=


where U

N

= phase to earth voltage

127V if 100V < V

meas

< 150V

230V if 150V < V

meas

≤ 265V


SAVING:

The tests can be stored pressing the

SAVE key twice

(according to paragraph 5.1).



Value of phase to
earth fault
impedance
expressed in

Ω.

Phase to earth
effective voltage
value expressed
in Volt.

Effective value of the phase to earth prospective
short circuit current expressed in Ampere
calculated according to the following formula.

SAVE

START

STOP