HT instruments MACROTEST 5035 User Manual
Page 53

MACROTEST
5035
EN - 52
At the end of the test the instrument
displays the values alongside.
ρ
36.5
Ω
m
2 0.93 Ω
CAUTION
The display of
“Measuring” means that the instrument is measuring. During
this phase never disconnect test leads.
SAVING:
The tests can be stored pressing the
SAVE key twice
(according to paragraph 5.1).
Note: If
START/STOP key was kept pressed, the instrument takes more consecutive
tests.
8. When a new value is acquired the instrument emits a short sound and calculates the
new average value.
9. Press
DISP key to show how many measurements are in average value
calculation and the measuring mode.
10. Press
CLR key if you want to cancel the medium value of the resistance
and the no. of measurements which are included in the calculation.
Note: Any test with result over 1999
Ω is not inserted in the calculation of medium value.
Example: 1
st
measurement (D=1):
main display: 6,6
Ωm
secondary display: 6,6
Ωm
2
nd
measurement (D=1):
main display: 4,15
Ω
secondary display: 2,61
Ω
3
rd
measurement (not inserted in the medium value)
main display: >1999
Ω
secondary display: 2,61
Ω
Earth resistivity value
CLR
DISP
SAVE