Macrotest 5035, En - 62, General rcd with i – HT instruments MACROTEST 5035 User Manual

Page 63: 10ma

Advertising
background image

MACROTEST

5035

EN - 62

Tripping time (t

N

)

Measuring range (ms)

Resolution (ms)

Accuracy

½ I

∆N

, I

∆N

1

÷999

2 I

∆N

1

÷200 general

1

÷250 selective

5 I

∆N

RCD (*)

1

÷50 general

1

÷160 selective

1

±(2% rdg + 2 dgt)

(*) ”Man 5 I

∆n

” and “AUTO” test modes aren’t available for RCD type A

500mA


- Earth resistance R

A

without RCD tripping

Measuring range (

) Resolution

(

)

Accuracy

1

÷ 1999

1

-0%, +(5% rdg + 3 dgt)

Test current

0.5 I

∆N

set in U

t

test mode

15mA in Ra 15mA test


Tripping current for RCD type A and AC

General RCD with I

∆N

≤ 10mA

RCD type

Measuring range I

N

(mA)

Resolution (mA)

Accuracy

AC

(0,5

÷ 1,4) I

∆N

0,1 I

∆N

-0%, +10% I

∆N

A

(0,5

÷ 2,4) I

∆N

General RCD with I

∆N

> 10mA

RCD type

Measuring range I

N

(mA)

Resolution (mA)

Accuracy

AC

(0,5

÷ 1,4) I

∆N

0,1 I

∆N

-0%, +10% I

∆N

A

(0,5

÷ 2) I

∆N


AC voltage

Measuring range (V)

Resolution (V)

Accuracy

0

÷ 460

1

±(3% rdg + 2 dgt)


Frequency

Measuring range (Hz)

Resolution (Hz)

Accuracy

47,0

÷ 63,6

0,1

±(0,1% rdg + 1 dgt)


Line impedance (phase to phase or phase to neutral)

Measuring range (

) Resolution

(

)

Accuracy

0,01

÷ 19,99

0,01

±(5% rdg + 3 dgt)

20,0

÷ 199,9

0,1

Max peak test current

127V

3,65A

230V

6,64A

400V

11,5A

Phase to phase test voltage

100

÷ 460V 50Hz ±0,5Hz

Phase to neutral test voltage

100

÷ 265V 50Hz ±0,5Hz


Fault loop impedance

Measuring range (

) Resolution

(

)

Accuracy

0,01

÷ 19,99

0,01

±(5% rdg + 3 dgt)

20,0

ч 199,9

0,1

200

ч 1999

1

Max peak test current

127V

3,65A

230V

6,64A

Phase to earth test voltage

100

÷ 265V 50Hz ±0,5Hz