Macrotest 5035, En - 62, General rcd with i – HT instruments MACROTEST 5035 User Manual
Page 63: 10ma

MACROTEST
5035
EN - 62
Tripping time (t
∆N
)
Measuring range (ms)
Resolution (ms)
Accuracy
½ I
∆N
, I
∆N
1
÷999
2 I
∆N
1
÷200 general
1
÷250 selective
5 I
∆N
RCD (*)
1
÷50 general
1
÷160 selective
1
±(2% rdg + 2 dgt)
(*) ”Man 5 I
∆n
” and “AUTO” test modes aren’t available for RCD type A
500mA
- Earth resistance R
A
without RCD tripping
Measuring range (
Ω) Resolution
(
Ω)
Accuracy
1
÷ 1999
1
-0%, +(5% rdg + 3 dgt)
Test current
0.5 I
∆N
set in U
t
test mode
15mA in Ra 15mA test
Tripping current for RCD type A and AC
General RCD with I
∆N
≤ 10mA
RCD type
Measuring range I
∆N
(mA)
Resolution (mA)
Accuracy
AC
(0,5
÷ 1,4) I
∆N
0,1 I
∆N
-0%, +10% I
∆N
A
(0,5
÷ 2,4) I
∆N
General RCD with I
∆N
> 10mA
RCD type
Measuring range I
∆N
(mA)
Resolution (mA)
Accuracy
AC
(0,5
÷ 1,4) I
∆N
0,1 I
∆N
-0%, +10% I
∆N
A
(0,5
÷ 2) I
∆N
AC voltage
Measuring range (V)
Resolution (V)
Accuracy
0
÷ 460
1
±(3% rdg + 2 dgt)
Frequency
Measuring range (Hz)
Resolution (Hz)
Accuracy
47,0
÷ 63,6
0,1
±(0,1% rdg + 1 dgt)
Line impedance (phase to phase or phase to neutral)
Measuring range (
Ω) Resolution
(
Ω)
Accuracy
0,01
÷ 19,99
0,01
±(5% rdg + 3 dgt)
20,0
÷ 199,9
0,1
Max peak test current
127V
3,65A
230V
6,64A
400V
11,5A
Phase to phase test voltage
100
÷ 460V 50Hz ±0,5Hz
Phase to neutral test voltage
100
÷ 265V 50Hz ±0,5Hz
Fault loop impedance
Measuring range (
Ω) Resolution
(
Ω)
Accuracy
0,01
÷ 19,99
0,01
±(5% rdg + 3 dgt)
20,0
ч 199,9
0,1
200
ч 1999
1
Max peak test current
127V
3,65A
230V
6,64A
Phase to earth test voltage
100
÷ 265V 50Hz ±0,5Hz