HT instruments MACROTEST 5035 User Manual
Page 21

MACROTEST
5035
EN - 20
Note: According to standard praxis it is recommended to effect RCD test both with phase
0° and with phase 180°. Therefore the test is to be repeated for both phase valves
of test current. If the RCD under test is of a type (which means sensitive to both
AC and unidirectional pulsing leakage currents) it is advisable to effect the test
both with sine wave and unidirectional pulse current with phase 0° and 180°.
The key
U
n
/I
∆n
permits to select one of the following rated tripping currents of
the RCD (which can be shown cyclically when pressing the key):
10mA.
30mA.
100mA.
300mA.
500mA.
The key
S▲ permits to activate the test for general or selective RCDs:
if the test is effected for
selective RCDs the symbol
S
must be
displayed.
if the test is effected for
general RCDs the symbol
S
must be NOT
displayed.
The option for testing the selective RCDs requires an interval among the
tests of 60 seconds (30 seconds in case of tests at ½ I
∆n
). A timer is
displayed indicating the waiting time for the instrument to effect the test
automatically.
Example:
Test on a RCD with rated current of I
∆n
=30mA selective
a) the instrument effects the test at ½ I
∆n
0°. If the RCD passed
the test, the message “OK” is displayed and the RCD does
not trip.
b) The instrument effects the test at ½ I
∆n
180°. If the RCD
passed the test, the message “OK” is displayed and the
RCD does not trip. At this stage 30 seconds elapse before
effecting next test.
c) The instrument effects the test at I
∆n
0°. If the RCD passed
the test, the message “OK” is displayed and the RCD trips
and the blinking symbol “rcd” is displayed. The operator
shall switch on the RCD. Anyway after the RCD tripping at
least 60 seconds will elapse before affecting next test
d) The instrument effects the test at I
∆n
180°. Follow the same
procedure as described under c)
e) The instrument effects the test at 5I
∆n
0°. Follow the same
procedure as described under c).
f) The instrument effects the test at 5I
∆n
180°. Follow the same
procedure as described under c). The test is completed
In case of AUTO working mode the operator shall switch the RCD on whenever the
instrument displays the blinking symbol
“rcd” signaling the RCD tripping
Note: On selective RCDS it is possible to carry out the following tests ”Man ½ I
∆n
”, ”Man
1 I
∆n
”, ”Man 2 I
∆n
”, ”Man 5 I
∆n
”, “AUTO”.
U
n
/I
∆n
DIST
S▲