Saved alarms (Err-LED is lit) can be acknowledged and deleted with the digital

input di1/2/3, the è-key or the Ò-key.

Configuration, see page 37: ConF / LOGI / Err.r

g

If an alarm is still valid that means the cause of the alarm is not removed so far

(Err-LED blinks), then other saved alarms can not be acknowledged and deleted.
Self-tuning heating ( ADA.H) and cooling ( ADA.C) error status:

3.5 Self-tuning

For determination of optimum process parameters, self-tuning is possible.

After starting by the operator, the controller makes an adaptation attempt,

whereby the process characteristics are used to calculate the parameters for fast

line-out to the set-point without overshoot.

The following parameters are optimized when self-tuning:

Parameter set 1:

Pb1

- Proportional band 1 (heating) in engineering units [e.g. °C]

ti1

- Integral time 1 (heating) in [s]

r only, unless set to OFF

td1

- Derivative time 1 (heating) in [s]

r only, unless set to OFF

t1

- Minimum cycle time 1 (heating) in [s]

r only, unless Adt0 was set to “no self-tuning” during

configuration by means of 8800/8840 Configurator.

Pb2

- Proportional band 2 (cooling) in engineering units [e.g. °C]

Operation

8840 profiler

15

Self-tuning

Error status Description

Behaviour

0

No error

3

Faulty control action Re-configure controller (inverse

i

direct)

4

No response of process

variable

The control loop is perhaps not closed: check sensor,

connections and process

5

Low reversal point

Increase ( ADA.H) max. output limiting Y.Hi or

decrease ( ADA.C) min. output limiting Y.Lo

6

Danger of exceeded

set-point (parameter

determined)

If necessary, increase (inverse) or reduce (direct) set-point

7

Output step change

too small (∆y > 5%)

Increase ( ADA.H) max. output limiting Y.Hi or reduce

( ADA.C) min. output limiting Y.Lo

8

Set-point reserve too

small

Acknowledgment of this error message leads to switch-over

to automatic mode.If self-tuning shall be continued,

increase set-point (invers), reduce set-point (direct)

or decrease set-point range

(r PArA / SEtp / SP.LO and SP.Hi )

9

Impulse tuning failed The control loop is perhaps not closed: check sensor,

connections and process