West Control Solutions N8840 User Manual

Page 34

Advertising
background image

1 with current and voltage input signals, scaling is required (see chapter 5.3)

Configuration level

Configuration parameters

34

8840 profiler

Name

Value range Description

Default

S.tYP

Sensor type selection

30

0

thermocouple type L (-100...900°C) , Fe-CuNi DIN

1

thermocouple type J (-100...1200°C) , Fe-CuNi

2

thermocouple type K (-100...1350°C), NiCr-Ni

3

thermocouple type N (-100...1300°C), Nicrosil-Nisil

4

thermocouple type S (0...1760°C), PtRh-Pt10%

5

thermocouple type R (0...1760°C), PtRh-Pt13%

6

thermocouple type T (-200...400°C), Cu-CuNi

7

thermocouple type C (0...2315°C), W5%Re-W26%Re

8

thermocouple type D (0...2315°C), W3%Re-W25%Re

9

thermocouple type E (-100...1000°C), NiCr-CuNi

10

thermocouple type B (0/100...1820°C), PtRh-Pt6%

18

special thermocouple

20

Pt100 (-200.0 ... 100,0 °C)

21

Pt100 (-200.0 ... 850,0 °C)

22

Pt1000 (-200.0 ... 850.0 °C)

23

special 0...4500 Ohm (preset to KTY11-6)

24

special 0...450 Ohm

30

0...20mA / 4...20mA 1

41

special -2,5...115 mV 1

42

special -25...115 0mV 1

50

potentiometer 0...160 Ohm 1

51

potentiometer 0...450 Ohm 1

52

potentiometer 0...1600 Ohm 1

53

potentiometer 0...4500 Ohm 1

S.Lin

Linearization

(only at S.tYP = 23,24,30,41 and 42 adjustable)

0

0

none

1

Linearization to specification. Creation of linearization table

with 8800/8840 Configurator (engineering tool) possible.

The characteristic for KTY 11-6 temperature sensors is

preset.

Corr

Measured value correction / scaling

(only at S.tYP = 23,24,30,41 and 42 adjustable)

0

0

Without scaling

1

Offset correction (at CAL level)

2

2-point correction (at CAL level)

3

Scaling (at PArA level)

In.F

-1999...9999

Alternative value for error at INP3

OFF

fAI3

Forcing INP3 (only visible with 8800/8840 Configurator!)

0

0

No forcing

1

Forcing via serial interface

Advertising