Configuration 31, Prog, Inp.1 – West Control Solutions N8840 User Manual

Page 31

Advertising
background image

Configuration level

8840 profiler

31

Configuration parameters

Name

Value range Description

Default

rnG.L

-1999...9999

X0 (low limit range of control) 1

-100

rnG.H

-1999...9999

X100 (high limit range of control) 1

1200

CYCL

Characteristic for 2-point- and 3-point-controllers

0

0

standard

3

with constant cycle (see page 48)

tunE

Auto-tuning at start-up (see page 15 )

0

0

At start-up with step attempt, at set-point with impulse

attempt

1

At start-up and at set-point with impulse attempt. Setting for

fast controlled systems (e.g. hot runner control)

2

Always step attempt at start-up

Strt

Start of auto-tuning

0

0

Manual start of auto-tuning

1

Manual or automatic start of auto-tuning at power on or

when oscillating is detected

Adt0

Optimization of T1, T2 (only visible with 8800/8840

Configurator!)

0

0

Automatic optimization

1

No optimization

1 rnG.L and rnG.H are indicating the range of control on which e.g. the

self-tuning is refering

Prog

Name

Value Range Description

Default

t.bAS

Timebase of Programmer

0

0

hours [hh] : minutes [mm]

1

minutes [mm] : seconds [ss]

InP.1

Name

Value range Description

Default

I.fnc

INP1 function selection

7

0

No function (following INP data are skipped)

1

Heating current input

2

External set-point SP.E (switch-over -> LOGI/ SP.E)

3

Position feedback Yp

4

Second process value x2 (ratio, min, max, mean)

5

External positioning value Y.E

(switch-over r LOGI / Y.E)

6

No controller input (e.g. limit signalling instead)

7

Process value x1

Advertising