3.5.5 Self-tuning cancellation

By the operator:

Self-tuning can always be cancelled by the operator. For this, press Ù and È

key simultaneously.With controller switch-over to manual mode after self-tuning

start, self-tuning is cancelled. When self-tuning is cancelled, the controller will

continue operating using the old parameter values.
By the controller:

If the Err LED starts blinking whilst self-tuning is running, successful self-tuning

is prevented due to the control conditions. In this case, self-tuning was cancelled

by the controller. The controller continues operating with the old parameters in

automatic mode. In manual mode it continues with the old controller output

value.

3.5.6 Acknowledgement procedures in case of unsuccessful self-tuning

1. Press keys Ù and È simultaneously:

The controller continues controlling using the old parameters in automatic

mode. The Err LED continues blinking, until the self-tuning error was

acknowledged in the error list.

2. Press key Ò (if configured):

The controller goes to manual mode. The Err LED continues blinking,

until the self-tuning error was acknowleged in the error list.

3. Press key Ù :

Display of error list at extended operating level. After acknowledgement

of the error message, the controller continues control in automatic mode using

the old parameters.

Cancellation causes:

r page 15: "Error status self-tuning heating ( ADA.H) and cooling ( ADA.C)"

Operation

Self-tuning

22