Configuration 37, Out.1 – West Control Solutions N8840 User Manual

Page 37

Advertising
background image

Configuration level

8840 profiler

37

Configuration parameters

Name

Value range Description

Default

HC.AL

Alarm heat current function (INP2)

0

0

switched off

1

Overload short circuit monitoring

2

Break and short circuit monitoring

LP.AL

Monitoring of control loop interruption for heating

0

0

switched off / inactive

1

active.

If ti1=0 LOOP alarm is inactive!

Hour

OFF...999999

Operating hours (only visible with 8800/8840 Configurator!)

OFF

Swit

OFF...999999

Output switching cycles (only visible with 8800/8840

Configurator!)

OFF

Out.1

Name

Value range Description

Default

O.Act

Method of operation of output OUT1

0

0

direct / normally open

1

inverse / normally closed

Y.1

Controller output Y1

1

0

not active

1

active

Y.2

Controller output Y2

0

0

not active

1

active

Lim.1

Limit 1 signal

0

0

not active

1

active

Lim.2

Limit 2 signal

0

0

not active

1

active

Lim.3

Limit 3 signal

0

0

not active

1

active

LP.AL

Interruption alarm signal (LOOP)

0

0

not active

1

active

HC.AL

Heat current alarm signal

0

0

not active

1

active

HC.SC

Solid state relay (SSR) short circuit signal

0

0

not active

1

active

P.EnD

Message "Programm end"

0

0

not active

1

active

FAi.1

INP1 error signal

0

0

not active

1

active