1 preparation for self-tuning 16 – West Control Solutions N8840 User Manual

Page 16

Advertising
background image

ti2

- Integral time 2 (cooling) in [s]

r only, unless set to OFF

td2

- Derivative time 2 (cooling) in [s]

r only, unless set to OFF

t2

- Minimum cycle time 2 (cooling) in [s]

r only, unless Adt0 was set to “no self-tuning” during

configuration by means of 8800/8840 Configurator .

Parameter set 2: analogous to parameter set 1 (see page 25)

3.5.1 Preparation for self-tuning

w Adjust the controller measuring range as control range limits. Set

values rnG.L and rnG.H to the limits of subsequent control.

(Configuration rControllerr lower and upper control range limits)

ConF

r Cntr r rnG.L and rnG.H

w Determine which parameter set shall be optimized.

-

The instantaneously effective parameter set is optimized.

r Activate the relevant parameter set (1 or 2).

w Determine which parameter set shall be optimized (see tables above).
w Select the self-tuning method

see chapter 3.5.3

-Step attempt after start-up

-

Pulse attempt after start-up

-

Optimization at the set-point

3.5.2 Optimization after start-up or at the set-point

The two methods are optimization after start-up and at the set-point.

As control parameters are always optimal only for a limited process range,

various methods can be selected dependent of requirements. If the process

behaviour is very different after start-up and directly at the set-point, parameter

sets 1 and 2 can be optimized using different methods. Switch-over between

parameter sets dependent of process status is possible (see page 25).

Optimization after start-up: (see page 17)

Optimization after start-up requires a certain separation between process value

and set-point. This separation enables the controller to determine the control

parameters by evaluation of the process when lining out to the set-point.

This method optimizes the control loop from the start conditions to the set-point,

whereby a wide control range is covered.

We recommend selecting optimization method “Step attempt after start-up”

with tunE = 0 first. Unless this attempt is completed successfully, we

recommend a “Pulse attempt after start-up”.

Operation

Self-tuning

16

8840 profiler

Advertising