West Control Solutions N8840 User Manual

Page 41

Advertising
background image

Configuration level

8840 profiler

41

Configuration parameters

Name

Value range Description

Default

SP.2

Switching to second setpoint SP.2

0

0

no function (switch-over via interface is possible)

2

DI1 switches

3

DI2 switches (only visible with OPTION)

4

DI3 switches (only visible with OPTION)

5

è - key switches

SP.E

Switching to external setpoint SP.E

0

0

no function (switch-over via interface is possible)

1

always active

2

DI1 switches

3

DI2 switches (only visible with OPTION)

4

DI3 switches (only visible with OPTION)

5

è - key switches

Y2

Y/Y2 switching

0

0

no function (switch-over via interface is possible)

2

DI1 switches

3

DI2 switches (only visible with OPTION)

4

DI3 switches (only visible with OPTION)

5

è - key switches

6

Ò - key switches

Y.E

Switching to fixed control output Y.E

0

0

no function (switch-over via interface is possible)

1

always activated (manual station)

2

DI1 switches

3

DI2 switches (only visible with OPTION)

4

DI3 switches (only visible with OPTION)

5

è - key switches

6

Ò - key switches

mAn

Automatic/manual switching

0

0

no function (switch-over via interface is possible)

1

always activated (manual station)

2

DI1 switches

3

DI2 switches (only visible with OPTION)

4

DI3 switches (only visible with OPTION)

5

è - key switches

6

Ò - key switches

C.oFF

Switching off the controller

0

0

no function (switch-over via interface is possible)

2

DI1 switches

3

DI2 switches (only visible with OPTION)

4

DI3 switches (only visible with OPTION)

5

è - key switches

6

Ò - key switches