Set-point process value correcting variable – West Control Solutions N8840 User Manual

Page 19

Advertising
background image

Optimization-at-the-set-point procedure:

The controller uses its instantaneous parameters for control to the set-point. In

lined out condition, the controller makes a pulse attempt. This pulse reduces the

correcting variable by max. 20% 1, to generate a slight process value

undershoot. The changing process is analyzed and the parameters thus calculated

are recorded in the controller. The optimized parameters are used for line-out to

the set-point.

With a 3-point controller, optimization for the “heating“ or “cooling” parameters

occurs dependent of the instantaneous condition.

These two optimizations must be started separately.
1 If the correcting variable is too low for reduction in lined out condition it is

increased by max. 20%.

Operation

8840 profiler

19

Self-tuning

set-point

process value

correcting

variable

Optimization at the set-point

Advertising