C.106, C.107, Configuration – West Control Solutions KS 94 User Manual

Page 18

Advertising
background image

Use of an auxiliary variable and external y limiting:

CAux

COVC

(Auxiliary variable z via INP3/6)

(Output limiting)

00: no

01: X+Z in conjunction with the process value without differentiation

02: X+-dZ/dt in conjunction with the process value with differentiation

in both directions

03: X+dZ/dt in conjunction with the process value with differentiation

and positive change

04: X-dZ/dt in conjunction with the process value with differentiation

and negative change

05: Y+Z in conjunction with the correcting variable without

differentiation

06: Y+-dZ/dt in conjunction with the correcting variable with

differentiation in both directions

07: Y+dZ/dt in conjunction with the correcting variable with

differentiation and positive change

08: Y-dZ/dt in conjunction with the correcting variable with

differentiation and negative change

0: no external limiting

1: OVC+

2: OVC-

Set-point functions:

(only with option C, Wext and not with 3-element controller)

WTrac

dW

W Sel

(Behaviour of Wint when switching over from Wext to

Wint with the w tracking input switched on )

(Type of set-point

tracking.)

(MIN/MAX selection)

0: Set-point tracking

1: Process value tracking

0: additive

1: factor

0: no selection

1: Max selection Weff

2: Min selection Weff

Ratio functions: (only with ratio controller)

Ratio

XDp

(Ratio control function)

(Process value decimal point)

1: (x1 + N0) / x2

2: (x1 + N0) / (x1 + x2)

3: (x2 - x1 + N0) / x2

0: no digit behind decimal point

1: 1 digit behind decimal point

2: 2 digits behind decimal point

3: 3 digits behind decimal point

Configuration

Operating instruction KS94

20

More

More

C.106

CON1
Reglerzusatz 2

0.0.0.0

More

C.107

CON1
Reglerzusatz 3

1.00.2