10.7.2 Signal output 2 / OUT2

Used for configuring the source of output OUT2. This signal output is a universal output and can be

configured for extensive functions.

Main configuration:

Src

Type

Mode

(Signal source)

(Output stage)

(Motor actuator output action)

00: output switched off

01: controller output Y1/Yout1

02: controller output Y2/Yout2

25: alarm1 (limit1)

26: alarm2 (limit2)

27: alarm3 (limit3)

28: alarm4 (limit4)

0: relay (switching)

0: not selectable

1: direct / normally open

2: inverse / normally closed

10.7.3 Signal output 3 / OUT3

Used for configuring the source of output OUT3. This signal output is a universal

output and can be configured for extensive functions.

Main configuration:

Selection is only possible with option C fitted.

Src

Type

Mode

(Signal source)

(Output stage)

(Motor actuator output

action)

00: none (output switched off)

01: controller output Y1/Yout1

02: controller output Y2/Yout2

03: controller output Ypid

04: position feedback Yp

05: control deviation xw

10: process value xeff

11: process value x1

12: process value x2

13: process value x3

20: set-point Wint

21: ext. set-point Wext

22: ext. Offset dWe

23: set-point Weff

24: programmer Wprg

0: switched off

1: 0 ... 20 mA

(continuous

output)

2: 4 ... 20 mA

(continuous

output)

3: 0 / 20 mA (logic)

0: not selectable

1: direct / normally open

2: inverse / normally closed

Additional configuration:

The optional configuration can be used for determining the functions for signal post-processing.This

configuration word is displayed only with the option enabled.

Func

Dp

(Function selection for signal output processing)

(decimal point for xsi,x0,x100)

0: no function, signal is output directly (0%...100%)

1: scaling (reference values C.570 and C.571 are effective)

2: linearization (segment points xs1,ys1 ...)

0: no decimal point

1: 1 digit behind the decimal point

2: 2 digits behind the decimal point

3: 3 digits behind decimal point

Configuration

Operating instruction KS94

28

C.560

OUT3
Hauptkonfig.

10.1.1

More

C.565

OUT3
Zusatzkonfig.

1.0.0.0