10.7

OUTPT: outputs

10.7.1 Signal output 1 / OUT1

Used for configuring the source of output OUT1. This signal output is a universal

output which can be configured for extensive functions.

Main configuration:

Src

Type

Mode

(Signal source)

(Output stage)

(Motor actuator output action)

00: output switched of

01: controller output Y1/Yout1

02: controller output Y2/Yout2

03: output Ypid

04: position feedback Yp

05: controlling deviation Xw

10: process value Xeff

11: X1

12: X2

13: X3

20: set-point W

21: external set-point Wext

22: external offset dWe

23: set-point Weff

24: programmer set-point Wprg

25: alarm 1 (limit1)

26: alarm 2 (limit2)

27: alarm3 (limit3)

28: alarm 1 (limit4)

0: relay (switching)

1: 0 ... 20 mA (continuous output)

2: 4 ... 20 mA (continuous output)

3: 0 / 20 mA (logic)

0: not selectable

1: direct / normally open

2: inverse / normally closed

Additional configuration Out1:

Via the options configuration, the functionality for a signal post-processing stage

can be determined.

This configuration word is displayed only with the option enabled.

Func

Dp

(Function selection for signal

output processing)

(decimal point for xsi,x0,x100)

0: no function, signal is output

without change (0%...100%)

1: scaling (reference values C.510

and C.511 are effective)

0: no decimal point

1: 1 digit behind decimal point

2: 2 digits behind decimal point

3: 3 digits behind decimal point

X0:

(physical value at 0%)

Numeric value -999 ... 9999

x100:

(physical value at 0%)

Numeric value -999 ... 9999

Configuration

27

Operating instruction KS94

More

C.505

OUT1

0.0.0.0

Zusatzkonfig.

C.510

x0
Bezugswert 0%

0

C.511

x100
Bezugswert 100%

100