Configuration – West Control Solutions KS 94 User Manual
Page 27

x0:
(physical value at 0%)
numeric value -999 ... 9999
x100:
(physical value at 100%)
numeric value -999 ... 9999
The configuration parameters for linearization are stored as
follows.
C.572
xs1
C.573
ys1
value pair 1
C.574
xs2
C.575
ys2
value pair 2
C.576
xs3
C.577
ys3
value pair 3
a
Note that the input values (x-values)
must be entered in ascending order.
(xs1<xs2<xs3...)
C.578
xs4
C.579
ys4
value pair 4
C.580
xs5
C.581
ys5
value pair 5
C.582
xs6
C.583
ys6
value pair 6
C.584
xs7
C.585
ys7
value pair 7
C.586
xs8
C.587
ys8
value pair 8
The range for these configuration words is within -999 and
9999 or ‘——’ (switched off)!
10.7.4 Signal output 4 / OUT4
Used for configuring the source of output OUT4. This signal output can be
configured for extensive functions.
Main configuration:
Src
Type
Mode
(Signal source)
(Output stage)
(Actuator output action)
00: output switched off
01: controller output Y1/Yout1
02: controller output Y2/Yout2
25: alarm 1 (limit1)
26: alarm 2 (limit2)
27: alarm 3 (limit3)
28: alarm 4 (limit4)
29: programmer output 1
30: programmer output 2
31: programmer output 3
32: programmer output 4
33: program end
0: relay (switching)
0: not selectable
1: direct / normally open
2: inverse / normally closed
Configuration
29
Operating instruction KS94