11.5

Alarm function

Text 1

Description

Range

Default

LIM1 Alarm 1

LimL1

Low limit

-999 ... 9999

‘——’ (switched off)

LimH1

High limit

-999 ... 9999

‘——’ (switched off)

Lxsd1

Switching difference

-999 ... 9999

0

LIM2 Alarm 2

LimL2

Low limit

-999 ... 9999

‘——’ (switched off)

LimH2

High limit

-999 ... 9999

‘——’ (switched off)

Lxsd2

Switching difference

-999 ... 9999

0

LIM3 Alarm 3

LimL3

Low limit

-999 ... 9999

‘——’ (switched off)

LimH3

High limit

-999 ... 9999

‘——’ (switched off)

Lxsd3

Switching difference

-999 ... 9999

0

LIM4 Alarm 4

LimL4

Low limit

-999 ... 9999

‘——’ (switched off)

LimH4

High limit

-999 ... 9999

‘——’ (switched off)

Lxsd4

Switching difference

-999 ... 9999

0

11.6

Self-tuning

Text 1 Description

R/W Range

Def.

Tune Optimization

YOptm

Correcting variable whilst

process at rest

R/W -105 ... 105

0

dYopt

Step width during identification R/W 5 ... 100

100

POpt

Parameter set to be optimized

R/W 0 ... 3

1

Trig1

trigger point 1 (set 1i set 2) R/W -999 ... 9999 (Decimal point as configured in C.700; ODP)

Trig2

trigger point 2 (set 2 i set 3) R/W -999 ... 9999 (Decimal point as configured in C.700; ODP)

Trig3

trigger point 3 (set 3 i set 4) R/W -999 ... 9999 (Decimal point as configured in C.700; ODP)

ORes1

Self-tuning result during heating

R

0: Cancellation (during optimization preparation)

1: Cancellation (wrong output action)

2: Finished (successful optimization; reversal point found)

3: Cancellation (process does not react or is too slow)

4: Cancellation (reversal point found; estimation unsafe)

5: Cancellation (reversal point not found; estimation unsafe)

6: Finished (optimization cancelled due to exceeded set-

point risk; reversal point not reached so far;

estimation unsafe)

7: Cancellation (correcting variable too low {Y < 5%)

8: Cancellation (set-point reserve too low)

ORes2

Self-tuning result during cooling R 0 ... 8 (see ORes1)

Tu1

Delay time heating

R 000,0 ... 999,9 s

Vmax1

Vmax heating

R 000,0 ... 999,9 /s

Kp1

Process amplification heating

R 000,0 ... 999,9

Tu2

Delay time cooling

R 000,0 ... 999,9 s

Vmax2

Vmax cooling

R 000,0 ... 999,9 /s

Kp2

Process amplification cooling

R 000,0 ... 999,9

Parameters

39

Operating instruction KS94