5 source: input signal allocation 21, Configuration – West Control Solutions KS 94 User Manual

Page 19

Advertising
background image

Span start X0: (only with ratio controller)

Xmin:(min. process value limiting Xmin)

Numeric value: -999 ... 9999

Span end X100: (only with ratio controller)

Xmax:(max. process value limiting Xmax)

Numeric value: -999 ... 9999 and Xmin Xmax

Factor for stoichiometric ratio s: (only with ratio controller)

S:stoichiometric ratio

Numeric value: 00.00 ... 99.99 (2 fixed digits behind decimal point)

Programmer configuration:

(only with programmer configured)

PSel

PwrUp

PEnd

PStrt

(Source for program

selection)

(Behaviour with mains

recovery)

(Behaviour with

program end)

(Source for

Run/Stop)

0: program selection

via operation

1: program selection

via control input

0: continue program

1: stop program and switch over

to Wint

2: continue program after

automatic research

0: continue with following

program

1: following program and

reset (start required)

0: start/stop and

reset together*.

control with

int/ext (without

Option B)

1: start/stop and

reset separate.

(Option B)

3: continue program after successful automatic research

otherwise switch over to Wint

4: continue program at the time mark of mains recovery

*C.190; SWi/e select the source for int/ext-switching.

10.5

SOURCE: Input signal allocation

Input signal allocation is dependent of main controller configuration ‘C.100‘. this proposal must

always be checked before commissioning and corrected, if necessary. Therefore, input signal

allocation ‘SOURCE’ is no independent main item and considered as additional configuration of

‘CONTR’.

Signal allocation analog signals:

S X2

SWext

S dW

S Z

(Signal source for X2

with ratio and

three-element controller)

(Signal source for Wext

with controller with

external set-point)

(Signal source for W

with controller with

set-point offset

(Signal source for

auxiliary variable)

0: X2 switched off

1: X2 of INP5

2: X2 of INP3

0: Wext switched off

1: Wext of INP5

2: Wext of INP6

3: Wext of INP4

0: dW switched off

1: dW of INP5

2: dW of INP6

3: dW of INP4

0: z switched off

1: z of INP3

2: z of INP6

3: z of INP4

Configuration

21

Operating instruction KS94