10.6

INPUT: inputs

The signal inputs for the previously selected controller configuration are determined in this main

group. The signal inputs required for the selected controller function are displayed in the menu for

configuration. As during control function configuration, a large number of applications can also be

covered by determining the main configuration. At the second level, special cases can be matched and

adjusted by additional, optional configuration.Max. 5 signal inputs are provided on KS94. Analog

inputs INP1, INP5 and INP6 are always provided; INP3 and INP4 are optional inputs.

All analog inputs (whether or not used for control) can be used for monitoring purposes

(e.g. alarm processing).

10.6.1 Signal input 1 / INP1 (main variable x1)

Configuration is for main variable x1. This signal input is a universal input for which extensive

functions can be configured.

Main configuration:

The main configuration word is used for determination of input sensor type and

physical unit. Additional input configurations can be determined using the

additional configuration.

Type

Unit

Dp

(Sensor type)

(Unit)*

(Number of decimals)

Thermocouple:

00: Type L 0 ... 900 °C

01: Type J 0 ... 900 °C

02: Type K 0 ... 1350 °C

03: Type N 0 ... 1300 °C

04: Type S 0 ... 1760 °C

05: Type R 0 ... 1760 °C

06: Type T 0 ... 400 °C

07: Type W 0 ... 2300°C

08: Type E 0 ... 900 °C

09: Type B (0)...400

...1820°C

Resistance thermometer:

20: Pt 100 -99.9 ... 850.0 °C

21: Pt 100 -99.9 ... 250.0 °C

25: 2 x Pt 100 -99.9 ... 850.0

°C

26: 2 x Pt 100 -99.9 ... 250.0

°C

Standard signals:

30: 0 ... 20 mA

31: 4 ... 20 mA

32: 0 ... 10 V

33: 2 ... 10 V

Potentiometric transducer:

40: 0 ... 500 Ohm

0: at

Typ

30...40

1: °C

2: °F

0: no decimal point

1: 1 digit behind the

decimal point

2: 2 digits behind the

decimal point

3: 3 digits behind decimal point

only with type: 20 ... 40

* Unit settings for scaling of Typ 00...26. With Typ 30...40 the value is fixed to 0. For this case the unit to be displayed will be configured by C.801.

x0:

(physical value at 0%)

numeric value -999 ... 9999

select only with type = 30 ... 40

x100:

(physical value at 100%)

numeric value -999 ... 9999 , X0

X100!

select only with type = 30 ... 40

Configuration

23

Operating instruction KS94