10.7.5 Signal output 5 / OUT5

Used for configuring the source of output OUT1.. This signal output can be configured for extensive

functions.

Main configuration:

Src

Type

Mode

(Signal source)

(Output stage)

(Actuator output action)

00: output switched off

01: controller output Y1/Yout1

02: controller output Y2/Yout2

25: alarm 1 (limit1)

26: alarm 2 (limit2)

27: alarm 3 (limit3)

28: alarm 4 (limit4)

29: programmer output 1

30: programmer output 2

31: programmer output 3

32: programmer output 4

33: program end

0: relay (switching) 0: not selectable

1: direct / normally open

2: i nverse / normally closed

10.7.6 DO5,6 (digital control outputs)

Additional digital control outputs are configured!

Main configuration:

(digital control signal DO5)

Selection is possible with option C fitted.

Src

Mode

(Digital control signal DO5)

(Actuator output action)

00: output switched off

01: controller output Y1

34: status automatic=0 / manual=1

0: not selectable

1: direct / normally open

2: inverse / normally closed

Main configuration:

(Digital control signal DO6)

Selection is possible with option C fitted.

Src

Mode

(Digital control signal DO6)

(Motor actuator output

action)

00: output switched off

02: controller output Y2

35: status external=0 / internal=1

0: not selectable

1: direct / normally open

2: inverse / normally closed